Praesideo 3.5 Installation and User Instructions EN54-16: 2008

en 49

Clause / Requirement

13.6 Accessibility of indications and controls

Four access levels shall be provided on the VACIE, from access level 1 (most accessible) to access level 4 (least accessible). Manual controls at a given access level shall not be accessible at a lower access level.The following shall apply:

Compliance

Signature

Praesideo is compliant.

The Praesideo system offers three types of user accounts (with different access rights):

User: user account type that offers operational control of the system; meant for operational users of the Praesideo system;

Installer: user account type that offers operational control, configuration and diagnosis of the Praesideo system; meant for installers and/or configurators of the Praesideo system;

Administrator: user account type that offers full control of the system including user management, i.e. the ability to add and delete user accounts.

Access level 1 is intended for operational users of the Praesideo system. It provides direct (unrestricted) operational access to the Praesideo system via:

A call station that does not have access control (call station keys)

Access level 2 is intended for operational users of the Praesideo system. It provides operational access to the system after (some form of) identification. The Praesideo system enforces logical identification for the following access points:

A call station with access control (via numeric keypad); a pin code must be entered before the call station can be used

The open interface; a username and password are needed to connect to the Praesideo system via the Open Interface); the user of the Open Interface must at least have a user account of type ‘user’ (i.e. user, installer or administrator access rights)

Note that access level 2 can also be enforced for the access level 1 access points by means of physical access control, which restricts access to persons that possess the physical access device (e.g. key, access card, et cetera). This is applicable for:

Input contacts with physical access control; the system components offering the input contacts are located in a room/cabinet that is not generally accessible

The front panel menu (with physical access control); the system components that have a front panel menu are located in a room/cabinet that is not generally accessible

A call station with physical access control; the call station is located in a room/cabinet that is not generally accessible

Access level 3 is intended for installers and/or configurators of the Praesideo system. It provides access for configuration and diagnosis of the Praesideo system after logical and/or physical identification. This level of access is offered through:

The web interface offered by the web server of the network controller. A user name and password need to be provided to get access to this web interface. The user must have at least a user account of type ‘installer’ (i.e. Installer or administrator access rights). The web interface can be used for configuration and logical diagnosis of the system.

Physical access control by means of installing the system elements in a restricted environment, such as placing the 19”-units in a 19”-rack with key lock. This type of access can be used for physical diagnosis of the system, e.g. inspect interconnections.

Access level 4 is intended for maintenance personnel of the Praesideo system. It provides software/firmware upgrade of the Praesideo system components after logical identification. This level of access is offered through:

The file transfer application of the Praesideo system to transfer message sets to the network controller and upgrade the system software. A user name and password is needed to be able to use the File Transfer Application and get access to the network controller. The user must have at least a user account of type ‘Installer’ (i.e. installer or administrator access rights).