Praesideo 3.5 Installation and User Instructions EN54-16: 2008

en 38

Clause / Requirement

Compliance

Signature

8.6.2 The audible indication shall be silenced automatically

Since the Praesideo system does not offer automatic reset

 

if the VACIE is automatically reset from the fault warning

from the fault warning condition this requirement does not

 

condition.

need to be implemented.

 

8.6.3 If previously silenced, the audible indication shall

After the audible indication has been silenced (by

 

resound for each newly recognized fault.

acknowledging all faults) the Praesideo system will resound

 

 

 

the indication upon occurrence of a new fault or

 

 

 

reoccurrence of a previously resolved fault.

 

8.7

Reset of fault indications

Praesideo is compliant.

 

 

 

 

 

8.7.1

Indications of faults as required in 8.2 shall be

 

 

capable of being reset

 

 

a automatically when faults are no longer recognized,

The Praesideo system does not offer automatic reset of

 

and/or

faults

 

b by a manual operation at access level 2.

Faults can be manually reset by acknowledging and

 

 

 

resetting them individually or all in one action.

 

 

 

Acknowledging and/or resetting faults individually can be

 

 

 

done via the front panel menu of the Network Controller

 

 

 

and via the Open Interface. Acknowledging and/or

 

 

 

resetting all faults in one action can be done via the front

 

 

 

panel menu of the network controller, control input

 

 

 

contacts, call station keys or the Open Interface.

 

8.7.2 Following reset as specified in 8.7.1, the indication of

If any individual fault is reset while it is not actually resolved

 

the correct functional conditions corresponding to any

in the system, the Praesideo system will report the fault

 

received signals shall either remain or be re-established

again within 20 seconds. If all faults are reset in one action,

 

within 20 s.

all individual faults that are not actually resolved in the

 

 

 

system are reported again within 20 seconds.

 

8.8

Transmission of the fault warning condition

Praesideo is compliant.

 

The VACIE shall have provision for transmitting, by means

Output contact 5 of the Praesideo network controller is the

 

of at least general fault signal, all faults specified in 8. This

fixed Fault alarm indicator output. This relay output contact

 

fault signal shall also be given if the VACIE is de-energized.

indicates no fault when open (energized) and indicates a

 

 

 

fault when closed (de-energized). If the Praesideo system is

 

de-energized this output contact is closed, therefore the fault signal will also be given.