Bosch Appliances 3.5 manual Fault-warningcondition output signal

Models: 3.5

1 498
Download 498 pages 15.1 Kb
Page 63
Image 63
8.6 Fault-warning condition output signal

Praesideo 3.5 Installation and User Instructions ISO7240-16: 2007

en 63

8.6 Fault-warning condition output signal

The Praesideo network controller provides two predefined

 

The s.s.c.i.e. shall have an output to transmit the fault-

control outputs for audible and visual fault indicators with

 

warning condition specified in 8.2. The output signal shall

fail-safe behavior. When de-energized, the contacts of

 

be given if the s.s.c.i.e. is de-energized.

these control outputs are closed (activated).

 

 

 

 

Clause / Requirement

Compliance

Signature

9 Disabled condition - Optional function

 

 

9.3 Indication of specific disablements

 

 

9.3.1 Each emergency loudspeaker zone shall be indicated

The optional disablement condition is not supported by the

 

by means of separate light-emitting indicators and/or an

Praesideo system.

 

alphanumeric display. The indications shall not be

 

 

suppressed during the voice-alarm condition.

 

 

9.3.3 The same light-emitting indicator may be used as that

The optional disablement condition is not supported by the

 

for the indication of the corresponding fault, although the

Praesideo system.

 

indication shall be distinguishable. The same light-emitting

 

 

indicator and the same indication may be used to indicate a

 

 

disabled emergency loudspeaker zone and an emergency

 

 

loudspeaker zone under test.

 

 

 

 

 

Clause / Requirement

Compliance

Signature

10 Test condition - Optional function

The optional test condition is not supported by the

 

 

Praesideo system.

 

 

 

 

Clause / Requirement

Compliance

Signature

11 Manual mode control - Optional function

 

 

11.1.2 In the manual mode, the receiving and display of

Praesideo does not inhibit the receiving and display of

 

signals shall not be inhibited.

signals in the manual mode.

 

11.1.3 In the manual mode, any phased evacuation

Praesideo will resume manually overruled calls after the

 

sequence shall be halted. Returning the system to

overruling call has finished, providing that the overruled call

 

automatic mode shall reinstate the phased evacuation

was without live speech and had emergency priority.

 

sequence as if it had not been halted.

 

 

Bosch Security Systems 2011-02

Page 63
Image 63
Bosch Appliances 3.5 manual Fault-warningcondition output signal