Praesideo 3.5 Installation and User Instructions EN54-16: 2008

en 28

Clause / Requirement

5General requirements for indications 5.1 Display and functional conditions

5.1.1The VACIE shall be capable of unambiguously indicating the following functional conditions, as described in Clauses 6 to 9:

quiescent condition;

voice alarm condition;

fault warning condition;

disablement condition (option with requirements)

5.1.2The VACIE shall be capable of being simultaneously in any combination of the following functional conditions on different voice alarm zones:

voice alarm condition;

fault warning condition;

disablement condition (option with requirements).

5.2 Indication display

All mandatory indications shall be clearly identifiable, except where otherwise specified in this European Standard.

Compliance

Signature

Praesideo is compliant.

See Clauses 6 to 9.

The Praesideo system is capable of being simultaneously in the voice alarm condition and in the fault warning condition.

The voice alarm condition is indicated per system on each call station (system status LED) and on the display of the network controller (emergency menu). This system wide indication can be combined with the indication of the fault warning condition: each call station uses a different LED (power/fault LED) for indication of the fault warning condition; therefore both conditions can be indicated simultaneously. The display of the network controller can indicate both the voice alarm condition and the fault warning condition (note that it will only show one condition automatically, the voice alarm condition has precedence; the user is able to see the fault warning condition by navigating through the menu if both conditions apply to the system simultaneously).

To indicate the voice alarm condition per zone, the installer shall use a call station keypad kit with correctly connected red LEDs (see clause 13.9.1) with configuration of the ‘Zone status’.

The fault warning condition is indicated per system on each call station (power/fault LED) and on the display of the network controller (faults menu). This system wide indication can be combined with the indication of the voice alarm condition: each call station uses a different LED (system status LED) for indication of the voice alarm condition; therefore both conditions can be indicated simultaneously. The display of the network controller can indicate both the voice alarm condition and the fault warning condition (note that it will only show one condition automatically, the voice alarm condition has precedence; the user is able to see the fault warning condition by navigating through the menu if the system is in both conditions simultaneously).

The installer must configure zone names in a way that the zone name is visible in the fault logging and network controller display (see clause 8.2.7 for details). In this way faults are indicated per zone.

The optional disablement condition is not implemented in Praesideo.

Praesideo is compliant.

The Praesideo system uses the following color coding for indications throughout the system:

Green: system ok

Red: system/zone in voice alarm condition

Yellow: system in fault warning condition