Excluded clauses

Praesideo 3.5 Installation and User Instructions ISO7240-16: 2007

en 69

Excluded clauses

Clause / Requirement

Compliance

Signature

EN54-16, clause 12.1 Emergency microphone - option

 

 

with requirements.

 

 

c Where a pre-announcement attention drawing signal is

This clause is not part of ISO7240-16.

 

provided, an indicator adjacent to the microphone shall

 

 

show when the signal has finished and live speech can

 

 

commence.

 

 

 

 

 

Clause / Requirement

Compliance

Signature

EN54-16, clause 13.4.1 Electrical and other design

This clause is not part of ISO7240-16.

 

requirements

 

 

The processing of signals shall give the highest priority to

 

 

the voice alarm condition.

 

 

EN54-16, clause 13.13 Message store(s)

The NOTE is not part of ISO7240-16.

 

Pre-recorded messages shall be stored in non-volatile

 

 

memory that retains the messages when all power sources

 

 

are removed.

 

 

NOTE The use of tapes or magnetic or optical data disks

 

 

for the storage of emergency messages is not acceptable

 

 

at the time of drafting this European Standard

 

 

(see Annex C)

 

 

Bosch Security Systems 2011-02