Bosch Appliances 3.5 manual 10: Configure predefined calls, en, Configure Predefined Calls…

Models: 3.5

1 498
Download 498 pages 15.1 Kb
Page 464
Image 464
59.5.4.4Configure PC Call Station Zone Groups...

Praesideo 3.5 Installation and User Instructions 11 Optional Software

en 464

interconnections and give them a unique name for reference purposes.

These interconnections are only used for normal calls and emergency calls, not for BGM.

Outputs (zones) that are used for interconnections cannot be selected anymore as zone outputs for layout configuration, see section 59.5.4.7.

Inputs that are used for interconnections cannot be selected anymore as audio input for live speech, see section 59.5.4.4.

Note

Calls without live speech across multiple subsystems use tones generated in each subsystem individually and/or messages stored in each subsystem. These tones and/or messages are also logged as such. If these calls include live speech, then only tones and/or messages from the originating subsystem are used and passed to all other subsystems, as being live speech. This way, synchronization is preserved but tones and messages broadcast via the subsystems are not logged separately.

59.5.4.4Configure PC Call Station Zone Groups...

This item configures the special PC Call Station zone groups.

figure 59.9: Configure PC Call Station zone groups

PC Call Station zone groups exist only on the PC Call Station, not on the connected NCOs. Normal zones or zone goups that have been defined on an NCO can be added to such a group. This allows a PC Call Station zone group to contain zone groups from different NCOs, even a multi-NCO All Call zone group is possible. PC Call Station zone groups can be configured

for predefined calls, just like normal zones and NCO zone groups.

59.5.4.5 Configure Predefined Calls…

This item configures the predefined calls that can be made from the PC Call Station Clients.

figure 59.10: Configure predefined calls

Use the Add new, Delete and Copy to new icons to create new predefined calls and give them a unique name for reference purposes. This name will appear on the screen button of the PC Call Station Client for selecting this predefined call. It is also shown here in a copy of a PC Call Station Client button to check whether the name fits.

The checkbox Use for PC TI defines whether this predefined call can also be used by the PC Telephone Interface Client. If this checkbox is checked, then a Numerical alias must be entered for this predefined call. This field only accepts numbers and the number must be unique. This way users can call in to Praesideo, using a telephone, and select a predefined call with the numeric keypad of the telephone. See section 61.6. Predefined calls are similar to call macros in Praesideo. Each call must have a priority and can have a start tone, end tone, messages that can be repeated, and a live speech phase. The available tones and messages depend on what information was retrieved from the network controllers. It is important that all network controllers in the system have the same tone set and message set, because only tones and messages will be available for selections that exist on all configured and connected network controllers. In case of live speech an audio input must be selected on a unit in one of the systems,

Bosch Security Systems 2011-02

Page 464
Image 464
Bosch Appliances 3.5 manual 10: Configure predefined calls, en, 59.5.4.4Configure PC Call Station Zone Groups