Changed clauses

Praesideo 3.5 Installation and User Instructions ISO7240-16: 2007

en 66

Clause / Requirement

Compliance

Signature

17 Tests

All tests as asked for in the clauses of section 17 have been

 

 

carried out by an accredited certification body for

 

 

ISO7240-16 compliancy.

 

 

The Praesideo system has been found compliant to

 

 

ISO7240-16 and received a certification of compliancy.

 

 

 

 

Clause / Requirement

Compliance

Signature

18 Test report

The tester must take care of documenting the testing

 

 

programme and the results of the tests in a test report that

 

 

at least contains the information as listed in clause 18.

 

Changed clauses

 

 

 

 

 

Clause / Requirement

Compliance

Signature

4.3 Power supply

The installer must use power supplies and battery charging

 

Power-supply equipment shall comply with the

equipment in accordance with ISO7240-4, with separate

 

requirements of ISO 7240-4 and may be internal or external

wiring for mains (230Vac) and battery backup (48Vdc) from

 

to the s.s.c.i.e. cabinet.

the power supply to the Praesideo system.

 

The power supply may be shared with that of the

The power supply equipment must be installed in a

 

emergency detection system.

separate cabinet, not shared with the Praesideo system,

 

 

unless the combination of the actual power supply

 

 

equipment and Praesideo system elements in the same

 

 

cabinet has been certified.

 

 

The content of the ISO7240-16 certification is subject to

 

 

change. The most recent version of this certificate can be

 

 

found on www.boschsecurity.com.

 

 

The network controller and all amplifiers are supplied with a

 

 

mains supply and DC backup supply (48V) input. Switch

 

 

over between the both takes place automatically, without

 

 

any interruption or status change other than the power

 

 

supply related indications.

 

 

The installer must ensure that the output voltages of the

 

 

power supply equipment do not exceed the specifications

 

 

of the mains and battery inputs of the connected Praesideo

 

 

equipment.

 

 

 

 

Clause / Requirement

Compliance

Signature

8 Fault-warning condition

 

 

8.5 Reset of fault indications

 

 

8.5.2 Following the completion of the reset process, the

If any individual fault is reset while it is not actually resolved

 

indication of the correct functional conditions

in the system, the Praesideo system will report the fault

 

corresponding to any received signals shall either remain or

again within 100 seconds. If all faults are reset in one

 

be re-established within 100 s.

action, all individual faults that are not actually resolved in

 

 

the system are reported again within 100 seconds.

 

 

 

 

Clause / Requirement

Compliance

Signature

9 Disabled condition - Optional function

 

 

9.3 Indication of specific disablements

 

 

9.3.4 If the indication is on an alphanumeric display that

Praesideo does not support the optional function disabled

 

cannot simultaneously indicate all of the disablements

condition. See 9.

 

because of its limited capacity, at least the following shall

 

 

apply.

 

 

b Suppressed disablement indications shall be capable

 

 

of being displayed, independently of other indications,

 

 

by means of a manual operation at access level 1 or 2,

 

 

which interrogates only the disablement indications.

 

 

Bosch Security Systems 2011-02

Page 66
Image 66
Bosch Appliances 3.5 manual Changed clauses