Bosch Appliances 3.5 manual Overview, 51.1Introduction 51.2General events, 51.3Call events, Status

Models: 3.5

1 498
Download 498 pages 15.1 Kb
Page 413
Image 413
51 Overview

Praesideo 3.5 Installation and User Instructions 10 Events

en 413

51 Overview

51.1Introduction

51.2General events

General events contain information about special situations. For example, the connection of a unit to the system. See chapter 52 for a list of all general events.

51.3Call events

Call events contain information about calls in the system. For example, the start of a call. See chapter 53 for a list of all call events.

51.4Fault events

51.4.1 Introduction

Fault events contain information about faults in the system. For example, an overload of a power amplifier. See chapter 54 for a list of all fault events.

51.4.2 Status

Each fault event has a status (see table 51.1).

table 51.1 Fault event statuses

Status

Description

New

The fault event is a new fault

 

event. All fault outputs are

 

activated.

Acknowledged

The new fault event is

 

acknowledged. If all faults in the

 

system have been

 

acknowledged, all fault alarm

 

buzzer outputs are deactivated.

Resolved

The acknowledged fault event is

 

resolved.

Reset

The resolved fault event is reset.

 

If all faults in the system have

 

been reset, all Fault alarm

 

indicator outputs are

 

deactivated.

Note

A fault output is a control output that has been configured as an Fault alarm buzzer or as a Fault alarm indicator (see table 43.6).

51.4.3 Acknowledging fault events

51.4.3.1Introduction

New fault events can be acknowledged:

Using the network controller (see section 51.4.3.2).

Using control inputs or keys (see section 51.4.3.3).

Using the open interface (see section 51.4.3.4).

Using the Logging Viewer (see chapter 57).

Note

When all faults are acknowledged, the Fault alarm buzzer outputs are deactivated.

51.4.3.2 Network controller

New fault events can be acknowledged using the Faults... menu of the network controller (see section 5.6.5). Using this menu it is possible to acknowledge individual fault events as well as all new fault events in the system.

51.4.3.3 Control input or key

New fault events can be acknowledged using control inputs or keys to which an Acknowledge/Reset action has been assigned (see section 47.3.23). However, such a control input or key acknowledges all new fault events in the system. It is not possible to acknowledge individual faults using a control input or key.

51.4.3.4 Open interface

New fault events can be acknowledged using the open interface (see the Open Interface Programming Instructions).

51.4.4 Resolving fault events

Before acknowledged fault events can be reset, they first must be resolved. Most fault events are automatically resolved by the system when the fault situation no longer exists. Others need to be resolved manually.

Manual resolving is needed for faults whose presence is not checked again after they occurred (for example, an amplifier overload). After solving the problem, the fault status of these fault events must be manually set to Resolved. This is done by resetting the fault, after which the system checks the presence of the fault again. If the fault is not present anymore, the status of the fault event is set to Resolved and then to Reset. If the fault is still present, a new fault event is created.

Bosch Security Systems 2011-02

Page 413
Image 413
Bosch Appliances 3.5 Overview, 51.1Introduction 51.2General events, 51.3Call events, 51.4Fault events, Status, Resolved