Bosch Appliances 3.5 manual Clause / Requirement

Models: 3.5

1 498
Download 498 pages 15.1 Kb
Page 37
Image 37
Manual background

Praesideo 3.5 Installation and User Instructions EN54-16: 2008

en 37

Clause / Requirement

Compliance

Signature

dany short-circuit or interruption in the transmission path between the VACIE and fire alarm devices when used (see 7.8).

efailure of any power amplifier.

8.3Indication of faults related to the transmission path to the CIE (option with requirements)

The Praesideo system does not offer this functionality directly: control inputs are supervised, but control outputs are just voltage free relay contacts. The installer must create a feedback signal (corresponding to the transmission path status between the Praesideo system and the fire alarm device) to a supervised input contact of the Praesideo system.

All Praesideo power amplifiers are supervised for overload, overheating, short-circuit, ground short and amplifier defect.

The VACIE may have provision for an indication of faults related to the transmission path to the CIE. In this case, the short-circuit or interruption of the transmission path to the CIE shall be indicated by means of a separate light emitting indicator and/or an alphanumeric display.

8.4Indication of faults related to voice alarm zones (option with requirements)

All input contacts of the Praesideo system can be supervised for short and interruption.

Open Interface connections are supervised through keep- alive messaging.

Faults related to the transmission path to the CIE are therefore individually reported and can be inspected using the front panel menu of the network controller or the logging application. The faults are also reported through the general fault warning indication.

The VACIE may have provision for an indication of faults

Faults that occur in the Praesideo system are reported per

related to voice alarm zones. In this case the short-circuit or

defective input or output for fault allocation. When an

interruption of a voice alarm transmission path between the

individual fault is reported the name of the event originator

VACIE and the loudspeakers in that zone shall be indicated

(i.e. the location of the fault) is provided.

by means of a separate light emitting indicator per zone

 

and/or an alphanumeric display.

The installer must give audio outputs that are assigned to a

 

zone, clear names, identifying the zone. This way the event

 

originator field in the indication of the individual fault will

 

immediately show in which zone the fault has occurred.

 

Praesideo provides zone fault status indicators, assigned to

 

keypad kits. One or more zones can be configured to

 

control such an indicator.

8.5 System fault

Praesideo is compliant.

A system fault is a fault as specified in 14.4 Program

14.4 Program monitoring (see also Annex C)

monitoring (see also Annex C)or 14.6 Monitoring of memory

 

contents in the case of software controlled VACIE. A

 

system fault may prevent requirements of this European

 

Standard, other than those specified below, from being

 

fulfilled. In the event of a system fault at least the following

 

shall apply:

 

aa system fault shall be visibly indicated by means of the general fault warning indicator and a separate light emitting indicator on the VACIE. These indications shall not be suppressed by any other functional condition of the VACIE and shall remain until a manual reset and/or another manual operation at access level 2 or 3;

ba system fault shall be audibly indicated. This indication may be capable of being silenced.

8.6 Audible indication

8.6.1The audible indication of faults required in 8.2 shall be capable of being silenced manually at access level 1 or 2 at the VACIE. The same manual operation may be used as for silencing the voice alarm condition.

System faults are individually reported by the Praesideo system and can be inspected using the front panel menu of the network controller or the logging application.

Faults are also reported through a general fault warning indicator, connected to a control output that is configured as Fault alarm buzzer or visual Fault alarm indicator.

Both the individual fault indicator of each system fault and the general fault warning indicator are not suppressed by any other functional condition of the Praesideo system.

A control output contact of a Praesideo system component can be configured as Fault alarm buzzer. This output contact can be connected to a buzzer. This way all faults, including system faults, are indicated audibly.

The Fault alarm buzzer can be silenced by acknowledging all faults via a key or control input that is configured as Fault acknowledge key. The control output for the visual Fault alarm indicator is only deactivated upon resolving and resetting all fault conditions.

Praesideo is compliant.

The Fault alarm buzzer can be silenced by acknowledging all faults via a key or control input that is configured as Fault acknowledge key. Individual faults can also be acknowledged from the front panel menu of the network controller or via the Open Interface.

Bosch Security Systems 2011-02

Page 37
Image 37
Bosch Appliances 3.5 manual Clause / Requirement