Praesideo 3.5 Installation and User Instructions EN54-16: 2008

en 39

Clause / Requirement

Compliance

Signature

9 Disablement condition (option with requirements)

Praesideo does not support the disablement condition.

 

9.1 General requirements

 

 

9.1.1Disablements in accordance with the requirements of 9.4 shall inhibit all corresponding mandatory indications and/or outputs but shall not prevent other mandatory indications and/or outputs.

9.1.2The VACIE shall have provision to independently disable and re-enable the function specified in 9.4 by means of manual operations at access level 2.

9.1.3The VACIE shall be in the disabled condition while a disablement in accordance with the requirements of 9.4 exists.

9.1.4Disablement and re-enablement shall not be affected by a reset from the voice alarm condition or from the fault warning condition.

9.2 Indication of the disabled condition

The disabled condition shall be indicated visibly, by means of

aa separate light emitting indicator (the general disablement indicator), and

ban indication for each disablement, as specified in 9.3 and 9.4.

9.3 Indication of specific disablements

9.3.1Disablements shall either be indicated within 2 s of the completion of the manual operation or, where a disablement cannot be completed within 2 s, it shall be indicated within 2 s that the disabling process is running.

9.3.2The same light-emitting indicator may be used as that for the indication of the corresponding fault, although the indication shall be distinguishable.

9.3.3If the indication is on an alphanumeric display, which cannot simultaneously indicate all of the disablements because of its limited capacity, at least the following shall apply:

athe presence of disablement indications which have been suppressed shall be indicated;

bsuppressed disablement indications shall be capable of being displayed by means of a manual operation at access level 1 or 2 which interrogates only disablement indications.

9.4 Disablements and their indication

Voice alarm zones may be capable of being independently disabled and re-enabled. In this case the disablements shall be indicated by means of separate light emitting indicators per zone and/or an alphanumeric display. The indications shall not be suppressed during the voice alarm condition.

9.5 Transmission of the disablement condition

The VACIE shall have provision for transmitting, by means of a general disablement signal, all disablement conditions specified in this clause.