Bosch Appliances 3.5 manual Clause / Requirement

Models: 3.5

1 498
Download 498 pages 15.1 Kb
Page 42
Image 42
Manual background

Praesideo 3.5 Installation and User Instructions EN54-16: 2008

en 42

Clause / Requirement

Compliance

Signature

11 Interface to external control device(s) (option with

 

 

the requirements)

 

 

The VACIE may have provision for interfacing to external

Praesideo is compliant.

 

control device(s) such as standardized user interfaces

 

 

required by local regulations. In this case, the following

 

 

shall apply:

 

 

a the interface shall allow only access level 1 and 2

Using the Open Interface requires access level 2. The

 

functions;

Open Interface functionality is limited to call and BGM

 

 

(Background Music) control as well as acknowledge/reset

 

 

of fault and emergency states.

 

 

Praesideo provides control input contacts with supervision

 

 

and control output contacts for external control devices,

 

 

with extensive configurable functionality.

 

b the mandatory functions of the VACIE shall not be

The Praesideo system operates as an autonomous system.

 

overridden;

All external activations are priority based to control

 

 

preference. By proper configuration system behavior is

 

 

tightly controlled and the mandatory functions of the VACIE

 

 

will not be overridden.

 

c any short-circuit , interruption or earth fault in the

 

 

transmission path to the external device(s) shall

 

 

1 not prevent the mandatory function of the VACIE,

The Praesideo system operates as an autonomous system,

 

and

so its operation (functionality) is not affected by loss of

 

 

connection to an Open Interface client.

 

2 be indicated on the VACIE, at least by means of the

The connection to an Open Interface client is monitored by

 

general fault warning indicator.

means of a keep-alive mechanism; if the connection is lost

 

 

the general fault warning indicator is activated and a

 

 

specific fault is reported.

 

NOTE - The external control devices should comply with

 

 

available local or national standards.

 

 

Bosch Security Systems 2011-02