15.4Installation

2011-02 Installation and User Instructions 5 Call Stations

en 206

15.4Installation

The call station basic is suitable for table-top use. Its functionality can be expanded by connecting:

Up to 16 call station keypads for pre-configured actions (LBB4432/00 or LBB4434/00).

Up to 15 call station keypads for pre-configured actions (LBB4432/00 or LBB4434/00) and one numeric keypad (PRS-CSNKP).

table 15.1: Power/Fault LED (left)

15.5Operation

The call station basic has three bi-color status LEDs that provide information about the call station basic and the status of the Praesideo system:

Power/fault LED (left), see table 15.1.

Call status LED (center), see table 15.2.

System status LED (right), see table 15.3.

Note

By default, the call station is delivered with factory firmware, which must be upgraded (see section 36.5). If the call station contains no firmware or damaged firmware (e.g. after an interrupted firmware upgrade), all LEDs are on.

Color

State

Explanation

---

Off

Power not available.

Green

On

Power on and no system or call station basic faults.

Yellow

Blinking

Power on, but there is a fault in the system.

Yellow

On

Power on, but there is a fault in the call station basic or the

 

 

Praesideo network is not operational.

table 15.2: Call status LED (center)

 

Color

State

Explanation

---

Off

No call status to display.

Green

On

Ready to talk/live announcement.

Green

Blinking

Chime on or pre-recorded message playing.

table 15.3: System status LED (right)

 

Color

State

Explanation

---

Off

No pre-defined or selected zones are in use or reserved by the

 

 

system, and no emergency announcement is being made.

Yellow

On

Lower priority announcements are being made or are reserved to

 

 

all or some of the zones which are pre-assigned to the

 

 

press-to-talk key of the call station basic and selected zones of

 

 

the keypad (if fitted).

Yellow

Blinking

Announcements with higher or the same priority (not emergency)

 

 

are on or reserved to all or some of the zones which are

 

 

pre-assigned to the press-to-talk key of the call station basic and

 

 

selected zones of the keypad (if fitted).

Red

On

An emergency announcement is being made.