EN54-16: 2008 compliancy checklist

Praesideo 3.5 Installation and User Instructions EN54-16: 2008

en 27

EN54-16: 2008 compliancy checklist

Clause / Requirement

4General requirements 4.1 General

4.1.1If an optional function with requirements is included in the VACIE, then all the corresponding requirements shall be met (see Annex B).

4.1.2If functions other than those specified in this European Standard are provided, they shall not jeopardize compliance with any requirements of this European Standard

4.2 Combined VACIE and CIE

When the VACIE and CIE are combined they may share common indications, manual controls and outputs (see Annex F). In this case, the following shall apply:

asingle fault in the CIE shall not adversely affect the mandatory functions of the VACIE;

bindication(s) and manual control(s) of the voice alarm condition shall be clearly identifiable, with the exception of the optional audible warning.

Compliance

Signature

Praesideo is compliant.

The following optional functions, with requirements, are included in Praesideo from version 3.3 upwards:

Audible warning (7.3)

Phased evacuation (7.5)

Manual silencing of the voice alarm condition (7.6.2)

Manual reset of the voice alarm condition (7.7.2)

Output to fire alarm devices (7.8)

Voice alarm condition output (7.9)

Indication of faults related to the transmission path to the CIE (8.3)

Indication of fault related to voice alarm zones (8.4)

Voice alarm manual control (10)

Interface to external control device(s) (11)

Emergency microphone(s) (12)

Redundant power amplifiers (13.14)

The following optional functions with requirements are not included in Praesideo:

Delay(s) to entering the voice alarm condition (7.4)

Disabled condition (9)

Praesideo power amplifiers and basic amplifiers shall not be configured to enter the power save mode when mains power fails. Although this would save battery power, the amplifier supervision and line/loudspeaker supervision is not active in this mode, which is a necessity for systems operating in accordance with EN54-16.

The Praesideo PC call station shall not be used as an emergency call station in systems operating in accordance to EN54-16. A PC does not comply with the requirements as set forward by this standard.

This requirement is not applicable. In Praesideo, the Voice Alarm Control and Indicating Equipment (VACIE) is not combined with a fire alarm Control and Indicating Equipment (CIE).

4.3 Power supply

Praesideo is compliant.

Power supply equipment, external or included in the

The installer must use power supplies and battery charging

VACIE, shall comply with the requirements of EN 54-4.

equipment in accordance with EN54-4, e.g. the Bosch

 

PRS-48CH12, with separate wiring for mains (230Vac) and

 

battery backup (48Vdc) from the power supply to the Praesideo

 

system.

 

The power supply equipment must be installed in a separate

 

cabinet, not shared with the Praesideo system, unless the

 

combination of the actual power supply equipment and

 

Praesideo system elements in the same cabinet has been

 

certified.

 

The content of the EN54-16 certification is subject to change.

 

The most recent version of this certificate can be found on

 

www.boschsecurity.com.

 

The network controller and all amplifiers are supplied with a

 

mains supply and DC backup supply (48V) input. Switch over

 

between the both takes place automatically, without any

 

interruption or status change other than the power supply related

 

indications.

 

The installer must ensure that the output voltages of the power

 

supply equipment do not exceed the specifications of the mains

 

and battery inputs of the connected Praesideo equipment.

NOTE - The power supply may be shared with that of

The power supply may be shared with that of a fire detection

the fire detection and fire alarm system.

system, but when operated with a battery a new capacity

 

calculation is required.