Chassis Installation and Grounding
AC Power Supply Tray
NOTE: No additional air space is needed above the AC Power Supply Tray when it is mounted directly below the Broadmore 1750 fan tray, which has a sloped bottom that does not interfere with air flow. Otherwise, provide at least 1.75 inch (1 RU) of free air space above the AC Power Supply Tray to ensure proper ventilation.
Perform the following steps:
1.Unpack and visually inspect the AC Power Supply Tray assembly.
2.For ease of rack installation, you can remove the power supply module(s) from the tray to make it lighter.
3.Adjust the rack mounting brackets for desired for a 19 or 23 inch rack and for front/rear mounting configuration. As shipped, the brackets will fit a 19” rack with
4.Rack mount the tray directly below the Broadmore 1750 using facility- provided mounting hardware.
5.Replace the power supply module(s) after
6.If the tray came with only one power supply module and a redundant power supply is to be installed, remove the blank cover on the front of the tray, insert the second power supply, and tighten the front panel screws.
Broadmore 1750 - Release 4.6 |