07.97 7 Drive Machine Data (SIMODRIVE Drive MD)
7.3.2 Drive MD (data description)
Table: Possible current and speed controller cycle combinations
SIN 840C with 611D
controller ...
Current
controller cycle
MD 1000
Speed
controller cycle
MD 1001 Comments
Single-axis performance 125 µs 125 µs Default value
Single-axis performance 62.5 µs 62,5 µs Minimum
Single-axis performance 125 µs 250 µs as from SW 6
Single-axis performance 125 µs 500 µs as from SW 6
2-axis performance 125 µs 125 µs Default value/minimum
2-axis performance
1 axis present 62.5 µs 62,5 µs Minimum
2-axis standard 125 µs 125 µs Default value/minimum
2-axis standard
1 axis present 125 µs 125 µs Default value/minimum
Notes:
Intermediate values are not permitted (parameterization error).
Exceeding the computing time on the speed controller clock cycle level is not permissible
and will lead to tripping of the drive.
Monitoring cycle
1002
Default value Lower input limit Upper input limit Units
100 000 4 000 100 000 µs
Active on
Power On
The interrupt clock cycle is used for high-priority monitoring purposes. Note: The input value
for the clock cycle must be a whole multiple of 4 ms (parameterization error). For the default
value, the monitoring cycle time is 100 ms.
m x 4000 µs m = 1, 2, 3 ... 25
Note:
The interrupts level must not be exceeded. If it is, the drive shuts down.
Configuration STS
1003
Default value Lower input limit Upper input limit Units
0330 0000 FFFF Hex
Active on
Power On
Caution:
Do not modify this machine data, the default corresponds to the optimum configuration. (For
Siemens service only)
© Siemens AG 1992 All Rights Reserved 6FC5197- AA50 7–75