09.95 10 Axis and Spindle Installation
10.4.3 Axis traversing
10.4.3 Axis traversing10.4.3.1 Traversing in jog mode
Prerequisites
All axis setpoint cables inserted.
Control direction correct.
Position control loops closed.
All gain values correct.
Safety signals active (EMERGENCY STOP, HARDWARE LIMIT SWITCH).
The following alarms can prevent axis traversing:
Description
Alarm No.
2000 ”EMERGENCY STOP"
148*
152*
188*
192*
Software limit switch approached (triggered by MD224*, 228*, 232*, 236*)
Software limit switch approached (triggered by MD224*, 228*, 232*, 236*)
Hardware limit switch approached
Hardware limit switch approached
168* Interface unit revoked servo enable for traversing axis
156* Set speed too high. Triggered by NC MD 264*.
112* Zero-speed monitor
Axis is not in position. Triggered by NC MD 372*
116* Contour monitor (triggered by NC MD 332*, 336*)
132*
136* Hardware measuring-circuit monitor
Measuring system dirty
The following additional signals (which do not trigger an alarm) are required for traversing in
jog mode:
No feed disable X, Y, Z, 4 - 9
No feed disable all
No axis disable X, Y, Z, 4 - 9
Servo enable X, Y, Z, 4 - 9
No follow-up mode X, Y, Z, 4 - 9
No parking axis X, Y, Z, 4 - 9
Pulse enable with
digital drive
Interface test