Page 278 of 894 NT5D33 and NT5D34 Lineside E1 Interface cards

Configuring parameters

The MMI has been designed with default settings so that no configuration is necessary. However, it can be configured based on the call environment.

Set Time

Before beginning to configure the MMI, login to the system and verify the current time. Do this by entering the Set Time (S T) command. The MMI displays the time it has registered. Enter a new time or hit Enter to leave it unchanged. The time is entered in the “hh:mm:ss,” the 24-hour, or military, format.

Set Date

Verify the current date. Do this by entering the Set Date (S D) command. The MMI then displays the date it has registered. Enter a new date or hit Enter to leave it unchanged. The date is entered in the “mm/dd/yy” format.

Set Alarm

The Set Alarm (S A) command sets the parameters by which an alarm is activated and the duration of the alarm after it is activated. There are three alarm levels as described below:

Alarm Level 0 (AL0) consists of activity with an error threshold below the AL1 setting, which is a satisfactory condition and no alarm is activated.

Alarm Level 1 (AL1) consists of activity with an error threshold above the AL1 setting, but below the AL2 setting that is deemed to be of minor importance. In this situation, the external alarm hardware is activated by closing the normally open contact, the RED ALARM LED on the faceplate lights, and an alarm message is created in the alarm log and the MMI terminal.

Alarm Level 2 (AL2) consists of activity with an error threshold above the AL2 setting which is deemed to be of major importance. In this situation, the following happens:

the external alarm hardware is activated by closing the normally open contact

the RED ALARM LED on the faceplate lights

553-3001-211 Standard 2.00 September 2004

Page 278
Image 278
Nortel Networks 553-3001-211 manual Configuring parameters, Set Alarm