Page 250 of 894 NT5D33 and NT5D34 Lineside E1 Interface cards

Power requirements

Table 89 shows the voltage and maximum current that the LEI requires from the backplane. One NT8D06 IPE Power Supply AC or NT6D40 IPE Supply DC can supply power to a maximum of eight LEIs.

Table 89

LEI card – power required

Voltage

Max. Current

 

 

5.0 V dc

1.6 Amp

+15.0 V dc

150 mA

-15.0 V dc

150 mA

 

 

Foreign and surge voltage protections

In-circuit protection against power line crosses or lightning strikes is not provided on the LEI. It does, however, have protection against accidental shorts to –52 V dc analog lines.

When the card is used to service off-premise terminal equipment through the public telephone network, install a Line Termination Unit (LTU) as part of the terminal equipment to provide external line protection.

Environmental specifications

Table 90 shows the environmental specifications of the LEI.

Table 90

LEI card – environmental specifications (Part 1 of 2)

Parameter

Specifications

 

 

Operating temperature – normal

15° to +30° C (+59° to 86° F), ambient

 

 

Operating temperature – short term

10° to +45° C (+50 to 113° F), ambient

 

 

Operating humidity – normal

20% to 55% RH (non-condensing)

 

 

Operating humidity – short term

20% to 80% RH (non condensing)

 

 

553-3001-211 Standard 2.00 September 2004

Page 250
Image 250
Nortel Networks 553-3001-211 manual Shows the environmental specifications of the LEI