Page 494 of 894 NT7D16 Data Access card

Large System

In Large Systems, the DAC is fully supported in IPE modules. These special slots on the DAC have 24-pair cables pre-wired to the Main Distribution Frame (MDF) in card slots 0-15. Any IPE slot will support the first four ports on the DAC if connections are made at the MDF. Most IPE modules can be upgraded to wire 24-pair cables to the MDF for all card slots.

Note: For directions concerning the pinouts for the MDF, refer to

Communication Server 1000M and Meridian 1: Large System

Installation and Configuration (553-3021-210).

Before you begin, power down:

the IPE module only, if it is a DC-powered system

the entire column, if it is an AC-powered system

It is recommended that you begin the installation from the right hand side (when facing the backplane), starting with slot 0 and moving towards slots on the left side. If you wish to add more than six DACs, and require slots 8 through 15, remove the input/output (I/O) panel. Be aware that a full shelf installation can take up to 3 hours. You need the following equipment to upgrade the cabling:

A0359946 Amphenol cables

These connectors include all the connector and screw apparatus.

You need one cable for each DAC.

cable ties

wire cutters

A3/16 nutdriver

System compatibility

To support the 24-pair requirement of the DAC, some cabling may need to be upgraded (Table 162). See “Upgrading systems” for more information.

Ports 0, 1, 2, and 3 of the DAC work in any standard 16-pair IPE slot (connect directly to the MDF).