Chapter 6 Cisco ASR 1002 Router Overview and Installation

Connecting Power to Cisco ASR 1002 Router

Warning Only trained and qualified personnel should be allowed to install, replace, or service this equipment.

Statement 1030

This section provides the procedures for connecting AC-input and DC-input power to your

Cisco ASR 1002 Router.

The DC power supply for the Cisco ASR 1006, ASR 1004, and ASR 1002 routers operate at individual specifications. Table 6-6shows the common input ranges and circuit breaker requirements.

 

Table 6-6

Cisco ASR 1000 Series Router DC Power Supply System Input Requirements

 

 

 

 

 

 

 

 

Cisco ASR 1000

 

 

 

 

 

 

 

Series Router DC

 

 

 

 

 

 

 

Power Supply

System Input Rating (Amps)

Circuit Breaker Amps

 

AWG # Wire

 

 

 

 

 

 

 

 

 

 

 

Minimum

Maximum

Minimum

 

Maximum

 

 

 

 

 

 

 

Cisco ASR 1006

40

 

Always 50

 

Always AWG #6 wire

 

 

 

 

 

 

 

 

Cisco ASR 1004

24

 

30

40

10

 

8

 

 

 

 

 

 

 

 

Cisco ASR 1002

16

 

20

30

12

 

10

 

 

 

 

 

 

 

 

For example, the Cisco ASR 1002 Router DC power supply, with 16 Amp input rating must use an AWG #12 gauge wire for a 20Amp circuit breaker and an AWG #10 gauge wire for a 30Amp circuit breaker.

Note All Cisco ASR 1000 Series Router AC power supplies require a 20 AMP circuit breaker.

Note Detailed instructions for removing and replacing the Cisco ASR1002 Router AC and DC power supplies are in Removing and Replacing a Cisco ASR 1002 Router Power Supply, page 8-40.

Read the safety warnings before you begin.

Warning Never install an AC power module and a DC power module in the same chassis. Statement 1050

Warning Installation of the equipment must comply with local and national electrical codes. Statement 1074

Warning When installing or replacing the unit, the ground connection must always be made first and disconnected last. Statement 1046

Warning This equipment must be grounded. Never defeat the ground conductor or operate the equipment in the absence of a suitably installed ground conductor. Contact the appropriate electrical inspection authority or an electrician if you are uncertain that suitable grounding is available. Statement 1024

 