Chapter 2 Cisco ASR 1000 Series Routers Components
Cisco ASR 1000 Series Router Power Supplies
AC Power System Output Voltage Alarm Range for Cisco ASR 1002
The AC power supply output voltage alarm occurs when the output voltage is below the low end of the minimum or above the high end of the maximum limits shown inTable
Table | Cisco ASR 1002 Router AC Power Supply Output Voltage Alarm Range | ||
|
|
|
|
|
| Minimum | Maximum |
|
|
|
|
12 V |
| 10.0 to 11.2V | 12.8 to 13.8 V |
|
|
|
|
3.3 V |
| 2.6 to 3.0V | None |
|
|
|
|
Cisco ASR 1002 Router DC Power Supply
This section provides information about the DC power supplies on the rear of the Cisco ASR 1002 Router. The recommended branch circuit breaker for the Cisco ASR 1002 Router DC power supply is 30Amp. Use an AWG #10 maximum wire gauge on the 30Amp circuit. The maximum branch circuit for the DC power supply module must not exceed 30Amp.
The Cisco ASR 1002 Router has two of the same type power supplies in power supply slot 0 and power supply slot 1. The power supply slot numbers are on the left side of the chassis and the power supplies are located on the floor of the chassis. The power supply switch is a Standby switch and is not considered a disconnect.
The DC input connector is a
The DC power supply unit is secured into the system chassis with two captive screws mounted on the faceplate.
Cisco ASR 1002 Router DC Power Supply LEDs and Connector
Figure 2-17 shows the DC power supplies at the rear of the Cisco ASR 1002 Router. The Cisco
ASR 1002 Router supports up to two power supplies. The power supply LEDs and connectors on the rear of the chassis are described in the Table 2-20.
|
| Cisco ASR 1000 Series Aggregation Services Routers Hardware Installation and Initial Configuration Guide |
|
| |
|
|
| |||
|
|
|
| ||
|
|
|
|