Chapter 6 Cisco ASR 1002 Router Overview and Installation

Installation Methods

The Cisco ASR 1002 Router DC power supply LEDs are defined inTable 6-3.

Table 6-3

Cisco ASR 1002 Router DC Power Supply LEDs

 

 

 

 

 

 

LED Label

 

LED

Color

Description

 

 

 

 

 

INPUT OK

 

A bi-color LED indicates

Green

LED illuminates green to signal that the DC power supply

 

 

presence of input voltage

 

input voltage is greater than 43.5VDC at turn-on and

 

 

 

 

remains green down to 39VDC.

 

 

 

 

 

 

 

 

Amber

The LED illuminates amber if the power supply turns off

 

 

 

 

due to low input voltage (falls below 39VDC) and

 

 

 

 

indicates that there is still a hazard present (voltage on the

 

 

 

 

terminal block). The LED remains amber and is active to

 

 

 

 

around 20V +/-5V. The LED is not illuminated if the input

 

 

 

 

is below 15V.

 

 

 

 

 

FAN OK

 

A bi-color LED indicates

Green

The LED illuminates s green when all fans are

 

 

power supply fan status

 

operational.

 

 

 

 

 

 

 

 

Red

The LED illuminates red when a fan failure is detected.

 

 

 

 

 

OUTPUT FAIL

 

Power supply activity

Red

When the LED is off, it signals that the DC output voltage

 

 

 

 

are within the normal operating range. Output voltage

 

 

 

 

between the minimum and maximum limits will not

 

 

 

 

create an output fail alarm, and output voltages below the

 

 

 

 

minimum or above the maximum will create an Output

 

 

 

 

Fail alarm.

 

 

 

 

Led illuminates red to indicate that the DC output is out

 

 

 

 

of the specified range.

 

 

 

 

When you turn the power supply on, the red LED

 

 

 

 

illuminates for two to three seconds to test LED operation

 

 

 

 

before going off.

 

 

 

 

 

The output voltage alarm is declared when the output voltage is below the low end of the minimum or above the high end of the maximum limits. When the output voltage is above the high end of the minimum or below the low end of the maximum limits, the Red state will not be activated.

Table 6-4shows the DC power supply output voltage alarm range.

Table 6-4

DC Power Supply Output Voltage Alarm Threshold Ranges

 

 

 

 

Output

 

Minimum

Maximum

 

 

 

 

12V

 

10.0-11.2V

12.8-13.8V

 

 

 

 

3.3V

 

2.6 - 3.0V

None

 

 

 

 

Installation Methods

Cisco ASR 1002 Router is designed for standalone, two rail 19-inch rack-mount (front rail only), four rail 19-inch rack-mount (front and rear rail).

Although rack-mounting is the preferred method of installation for the Cisco ASR 1002 Router, you can mount the chassis on an equipment shelf or tabletop.

Cisco ASR 1000 Series Aggregation Services Routers Hardware Installation and Initial Configuration Guide

 

OL-13208-03

6-9

 

 

 

Page 169
Image 169
Cisco Systems ASR 1000 Series manual Output Minimum Maximum, 12V 10.0-11.2V 12.8-13.8V None