set ia

Examples

Serial port configuration settings

 

The following “set ia” commands show the default serial-port configuration

 

settings for the Digi Connect WAN IA:

 

set ia serial=1 active=on type=slave protocol=modbusrtu table=1

 

set ia serial=1 messagetimeout=2500 slavetimeout=1000 chartimeout=20

 

set ia serial=1 priority=medium idletimeout=0

 

set ia serial=1 errorresponse=off broadcast=replace fixedaddress=0

 

set ia table=1 route=1 active=on type=serial protaddr=0-32 port=1

 

Note that future Digi Connect WAN IA firmware releases will expose these

 

configuration settings in the Web user interface.

 

Enable a Modbus/RTU serial master

 

To enable a Modbus/RTU serial master instead, change the configuration

 

settings by entering the following “set ia” commands via Telnet. These

 

“set ia” commands change the serial device type from slave to master. In

 

addition, to handle cellular latency, a timeout value of 31 seconds or longer

 

is needed. In addition, the first route, which forwards requests to the serial

 

port, can be turned off.

 

set ia serial=1 type=master messagetimeout=31000

 

set ia table=1 route=1 active=off

 

Additional examples

 

For more examples of the “set ia” command, see the application note

 

“Remote Cellular TCP/IP Access to Modbus Ethernet and Serial Devices”

 

(Part Number 90000773) available at available from digi.com Support

 

page: http://www.digi.com/support/ia

See also

"revert" on page 61. The “revert ia” command options revert any

 

existing IA configuration settings.

 

"set profile" on page 172. The “ia” port profile configures a serial port for

 

controlling and monitoring various IA devices and PLCs.

 

"set serial" on page 189.

 

"show" on page 249 for displaying the current IA configuration settings.

 

• For more information on Industrial Automation, see the IA application

 

help available at this URL: http://www.digi.com/support/ia