set profile
174 Chapter 2 Command Descriptions
tcp_sockets
Associates the TCP Sockets port profile with the port.
tunneling
Associates the Serial Bridge port profile with the port.
udp_sockets
Associates the UDP Sockets port profile with the port. Not supported
in Digi Connect WAN.
custom
Associates the Custom port profile with the port.
ia Associates the ia (Industrial Automation) port profile with the port.
The default configuration settings assume Modbus/RTU slaves with
addresses 1 to 32 are attached to the serial port. Default port
characteristics are 9600:8,N,1. Unit ID zero (0) is auto-mapped to
Modbus/RTU slave address 1. The electrical interface is set as EIA-
232, 422, or 485 by the four DIP switches on the bottom of the unit.
Example #> set profile port=1 profile=realport
See also "revert" on page 61.
"show" on page 249.
"set ia" on page 119 for a description of the default settings for Industrial
Automation.
For more information on port profiles, see the topic “About Port Profiles"
in the Digi Connect Family User’s Guide.