Configuration

6.7 Outputs Configuration

Overview

This group lets you select the signal that will be transmitted.

Accessing Outputs Menu

Press Setup to display the Main menu.

Use the keys to select “Outputs” then press Enter to enter the sub-menu.

Output 1, Output 2, or Output 3 and their associated parameters are available for selection.

Press

to highlight the desired menu selection then press Enter to display the

 

group of parameters.

 

Refer to “Section 6.4.1 - General Rules for Editing”.

 

 

 

Table 6-6 Outputs Configuration

 

 

 

 

 

Sub-menu

 

Parameter

Selection or Range

Parameter Definition

selection

 

 

 

of Setting

 

Output 1

 

Source

 

Any Analog Signal

Process Variable Source - Selects the signal

Output 2

 

 

 

See Table 6-3

that will be transmitted.

Output 3

 

 

 

 

See Note 1 for units.

 

 

 

 

 

 

 

 

 

 

 

 

High Range

-99999.00 to 99999.00

High Range Value - value of input that

 

 

 

 

 

corresponds to 100 % output value.

 

 

 

 

 

See Note 1 for units.

 

 

 

 

 

 

 

Low Range

-99999.00 to 99999.00

Low Range Value - value of input that

 

 

 

 

 

corresponds to 0 % output value.

 

 

 

 

 

See Note 1 for units.

 

 

 

 

 

 

 

Slew Time

0.000 to 999.00

Slew Time is the maximum rate of change

 

 

 

 

in seconds

required to drive the output from full OFF (0% -

 

 

 

 

default = 0.000

typically 4 mA) to full ON (100% - typically

 

 

 

 

 

20mA).

 

 

 

 

 

 

 

mA Range High

0 to 20

Value of mA output that corresponds to 100 %

 

 

 

 

default = 20

output signal (for example: 20 mA).

 

 

 

 

 

 

 

mA Range Low

0 to 20

Value of mA output that corresponds to 0 %

 

 

 

 

default = 4

output signal (for example: 4 mA).

 

 

 

 

 

 

 

mA Limit High

0 to 21

Value of mA that you want to set the High

 

 

 

 

default = 21

Range Limit.

 

 

 

 

 

 

 

mA Limit Low

0 to 21

Value of mA that you want to set the Low

 

 

 

 

default = 3

Range Limit.

 

 

 

 

 

 

74

UDA2182 Universal Dual Analyzer Product Manual

January 2009

Page 86