Outputs Calibration

Step

 

Action

 

 

Screen

8

 

 

 

 

 

 

Press

Enter

 

OUTPUT CAL

 

 

 

Output 1

 

 

 

 

 

 

Output 2

 

 

 

 

 

 

Output 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Use

to select

 

 

 

an Analog Output to be

 

 

 

calibrated

 

 

 

 

 

 

9

 

 

 

 

 

Enter

OUTPUT 1

 

Press

20mA Offset

 

0

 

 

 

4mA Offset

 

0

 

 

 

Reset 20mA Offs

 

 

 

Reset 4mA Offs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Use

to select

 

 

 

 

” 20 mA Offset”

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

Enter

 

OUTPUT 1

 

Press

 

20mA Offset

 

 

 

 

-147

 

 

 

 

 

4mA Offset

3

 

 

 

 

 

Reset 20mA Offs

 

 

 

 

Reset 4mA Offs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The right most digit will be

 

 

 

“blinking”.

 

 

 

11To correct the value on the meter:

Use the keys to increment or decrement the value of the digit

Use the keys to move the cursor to the next digit.

Repeat as required to achieve a 20mA reading on the test meter

When all digits have been changed, press “Enter” to store the 20mA value.

Press “Exit” to cancel. The previous value is retained.