Honeywell UDA2182 Accessing Control Menu, PIDn Config Table, PIDnAlarms Table, PID Configuration

Models: UDA2182

1 258
Download 258 pages 46.92 Kb
Page 106
Image 106

Configuration

Accessing Control Menu

(See “Maintenance” Menu item (Section 6.18), “System” selection to Enable PID Control)

Press Setup to display the Main menu.

Use the keys to select “PID Control” then press Enter menu.

PID Control 1 and 2 are divided into 3 sections:

PID(n) Config (Table 6-13),

PID(n)Tune (Table 6-14),

PID(n)Alarms (Table 6-15)

Press to highlight the desired menu selection then press group of parameters.

Refer to “Section 6.4.1 – “General Rules for Editing”.

Table 6-13 PID Configuration

to enter the sub-

Enter to display the

Sub-menu

Parameter

Selection or

Parameter Definition

selection

 

Range of Setting

 

PID 1 Config

PV Source

None

Process Variable Source

PID 2 Config

 

Input 1 PV (default)

 

 

 

Input 2 PV

 

 

 

 

 

 

PV High

-99999 to 99999

Input Range of the PV - High Range Value

 

 

default = High

These values are in units of that Input PV, such

 

 

Range of PV Input

as 0-14pH.

 

 

 

 

 

PV Low

-99999 to 99999

Input Range of the PV - Low Range Value

 

 

default = Low

These values are in units of that Input PV, such as

 

 

Range of PV Input

0-14pH.

 

 

 

 

 

SP High Limit

-99999 to 99999

Setpoint High Limit Value - prevents the

 

 

default = High

setpoint from going above the value set here.

 

 

Range of PV Input

 

 

 

 

 

 

SP Low Limit

-99999 to 99999

Setpoint Low Limit Value - prevents the

 

 

default = Low

setpoint from going below the value set here.

 

 

Range of PV Input

 

 

 

 

 

 

Output High Limit

-99999 to 99999

Output High Limit Value - is the highest value

 

 

default = 100.00

of output beyond which you do not want the

 

 

 

automatic output to exceed.

 

 

 

 

 

Output Low Limit

-99999 to 99999

Output Low Limit Value - is the lowest value of

 

 

default = 0.00

output beyond which you do not want the

 

 

 

automatic output to go below.

 

 

 

 

94

UDA2182 Universal Dual Analyzer Product Manual

January 2009

Page 106