Honeywell UDA2182 manual 9999 to, Enable default

Models: UDA2182

1 258
Download 258 pages 46.92 Kb
Page 108
Image 108

Configuration

Sub-menu

Parameter

Selection or

 

Parameter Definition

selection

 

Range of Setting

 

 

 

Bias

0.0 Default

 

Bias that is applied to the Remote Setpoint.

 

 

-9999 to 99999

 

 

 

 

 

 

 

 

RSP Select

Monitor (1 – 4)

 

When this input is ON, the Remote Setpoint is

 

 

Logic (1 – 4)

 

used. If set to None, the operator can select

 

 

Digital In (1 – 2)

 

the remote setpoint from the PID operator

 

 

 

 

 

 

 

 

display.

 

 

 

 

 

 

FF Source

Any Analog Signal

 

Feed Forward value that is applied to the

 

 

See Table 6-3

 

output. A change in the feed forward signal

 

 

 

 

input will result in a proportional change in the

 

 

 

 

output per the feed forward gain parameter.

 

 

 

 

 

 

FF Gain

1.000 (default)

 

Feed Forward Gain used to calculate the

 

 

0.1 to 1000.0

 

change in the PID output based upon a change

 

 

 

 

of the feed forward input signal.

 

 

 

 

 

 

TRC Select

Any Digital Signal

 

TRC (tracking control) – selects the tracking

 

 

See Table 6-4

 

mode

 

TRV Select

Any Analog Signal

 

TRV (tracking value) – is the commanded

 

 

See Table 6-3

 

 

 

 

output value in percentage

 

 

 

 

 

 

 

 

(PID Output = TRV Input when TRC = ON)

 

 

 

 

When TRC is active, the front-panel display will

 

 

 

 

indicate TRC for the PID loop.

 

 

 

 

Variables can be connected to TRC and TRV

 

 

 

 

to allow remote control of the PID output.

 

 

 

 

TRC can be connected to a digital variable

 

 

 

 

TRV can be connected to an analog variable

 

 

 

 

 

 

Manual Permit

Enable (default)

 

Allows the operator to select Manual Operation

 

 

Disable

 

of the PID loop from the PID Operator Display

 

 

 

 

 

 

Auto Permit

Enable (default)

 

Allows the operator to select Auto Operation of

 

 

Disable

 

the PID loop from the PID Operator Display

 

 

 

 

 

 

LSP Permit

Enable (default)

 

Allows the operator to select the Local Setpoint

 

 

Disable

 

from the PID Operator Display

 

 

 

 

 

 

RSP Permit

Enable (default)

 

Allows the operator to select the Remote

 

 

Disable

 

Setpoint from the PID Operator Display

 

 

 

 

 

96

UDA2182 Universal Dual Analyzer Product Manual

January 2009

Page 108
Image 108