Configuration

While TRV is active, the output can be adjusted using manual mode from the front-panel. After manual mode is terminated, the output will remain at the level because the output is tied to TRV.

ATTENTION

Upgrading software on the UDA2182 to a new version will remove PID control (on units where PID has been ordered or been added in the Field).

Therefore, the following steps need to be followed in order to retrieve that option:

If PID was ordered when the unit was originally ordered:

Retrieve your Unit ID by going to the MAINTENANCE Æ SYSTEM menu

Call GTS (1-800-423-9883)

Inform them that you are going to do a software upgrade and you need the Option ID for your unit (this is why you need the Unit ID)

Record Option ID for next step

After upgrading software, go to MAINTENANCE Æ SYSTEM menu and enter the recorded OPTION ID value.

The PID will have to be reconfigured to settings prior to upgrade.

If PID was added after the unit was originally shipped:

Before upgrading software, go to MAINTENANCE Æ SYSTEM menu and record the OPTION ID value.

After upgrading software, go to MAINTENANCE Æ SYSTEM menu and enter the recorded OPTION ID value.

The PID will have to be reconfigured to settings prior to upgrade.