Configuration

Sub-menu

Parameter

Selection or

 

Parameter Definition

selection

 

Range of Setting

 

 

 

Reset

-0.02 to 50

 

RESET (Integral Time) - adjusts the control

 

 

default = 1.000

 

output according to both the size of the

 

 

 

deviation (SP-PV) and the time it lasts. The

 

 

 

 

 

 

 

 

amount of corrective action depends on the

 

 

 

 

value of Gain.

 

 

 

 

The reset adjustment is measured as how

 

 

 

 

many times proportional action is repeated per

 

 

 

 

minute (Repeats/minute) or how many minutes

 

 

 

 

before one repeat of the proportional action

 

 

 

 

occurs (Minutes/repeat – default).

 

 

 

 

 

 

Tune Set 2

None (default)

 

Digital Source for selection of Tuning set 2.

 

 

Monitor 1

 

When active, this input will override the current

 

 

Monitor 2

 

 

 

Monitor 3

 

tuning set selection and force the PID to use

 

 

Monitor 4

 

tuning set 2. This applies for non-duplex type

 

 

Logic 1

 

control.

 

 

Logic 2

 

Note: For duplex control types, the tune set is

 

 

Logic 3

 

 

 

 

automatically select by the output zone (Tune

 

 

Logic 4

 

 

 

 

2 selected for Output < 50).

 

 

Digital In 1

 

 

 

 

 

 

 

Digital In 2

 

 

 

 

 

 

 

 

Gain or Prop Band 2

0.1 to 1000.0

 

Gain or Prop Band2 for Tuning Set 2. Same as

 

 

default = 1.000

 

Gain or Prop Band.

 

 

 

 

 

 

Rate 2

-0.035 to 10.000

 

Rate 2 for Tuning Set 2. Same as Rate.

 

 

default = 0.000

 

 

 

Reset 2

-0.02 to 50

 

Reset 2 for Tuning Set 2 Same as Reset.

 

 

default = 1.000

 

 

Table 6-15 PID Alarms

Sub-menu

Parameter

Selection or

Parameter Definition

selection

 

Range of Setting

 

PID 1 Alarms

Alm 1 SP1 Type

No Alarm (default)

Alarm 1 Setpoint 1 Type

PID 2 Alarms

 

PV High

High PV Alarm: PV > Alm SP

 

 

PV Low

Low PV Alarm: PV < Arm SP

 

 

Dev High

High Deviation Alarm: PV – SP > Alm SP

 

 

Dev Low

Low Deviation Alarm: PV – SP < Alm SP

 

 

SP High

High Setpoint Alarm: SP > Alm SP

 

 

SP Low

Low Setpoint Alarm: SP < Alm SP

 

 

Output High

High Output Alarm: Out > Alm SP

 

 

Output Low

Low Output Alarm: Out < Alm SP

 

 

 

 

 

Alm 1 SP1 Value

-99999 to 99999

Alarm 1 Setpoint 1 Value

 

 

default = 0.000

 

 

 

 

 

98

UDA2182 Universal Dual Analyzer Product Manual

January 2009

Page 110
Image 110
Honeywell UDA2182 manual PID Alarms, No Alarm default, PID 2 Alarms