Configuration

Accessing Auxiliary Menu

Press Setup to display the Main menu.

Use the keys to select “Auxiliary” then press Enter to enter the sub-menu.

Press

to highlight the desired menu selection then press Enter to display the

 

group of parameters.

 

 

 

 

Refer to “Section 6.4.1 – “General Rules for Editing”.

 

 

 

 

 

 

 

 

Table 6-12 Auxiliary Configuration

 

 

 

 

 

 

 

 

 

Sub-menu

 

Parameter

 

Selection or Range of Setting

 

Parameter Definition

selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Analog Signal Source – Process signal

Switch 1

 

In A Source

 

Any Analog Signal

Switch 2

 

In B Source

 

See Table 6-3

to be monitored by the Alarm. Any

 

 

 

 

analog source such as PV, Temperature,

 

 

 

 

 

 

 

 

 

 

 

 

Pharma, Math, Function Generator,

 

 

 

 

 

 

Switch, PID, or Calculated Values*

 

 

 

 

 

 

* units of measure between the two input

 

 

 

 

 

 

boards must be similar

 

 

 

 

 

 

 

 

 

Select B

 

 

Any Digital Signal

Digital Signal Source when active will

 

 

 

 

 

See Table 6-4

select the B input source of the switch as

 

 

 

 

 

 

the output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Switch

 

 

 

 

 

 

 

 

 

InA

 

 

 

 

 

 

 

 

 

InB

 

 

 

 

 

 

 

 

 

Select B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If Select B is OFF then Switch Output = In A

 

 

 

 

 

 

 

If Select B is ON then Switch Output = In B

 

 

 

 

 

 

 

Func Gen 1

 

Source

 

 

None

Function Generator selections have 2

Func Gen 2

 

 

 

 

Input 1 PV

input sources

 

 

 

 

 

Input 2 PV

(Input 1 PV and Input 2 PV).

 

 

 

 

 

PID 1 Out

 

 

 

 

 

 

 

 

 

PID 2 Out

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ATTENTION

The X (n) value must be < X(n+1) value. Thus, if fewer than 11 breakpoints are needed, be sure to configure any unneeded breakpoints with the same X and Y values used for the previous breakpoint.

90

UDA2182 Universal Dual Analyzer Product Manual

January 2009

Page 102
Image 102
Honeywell UDA2182 Accessing Auxiliary Menu, Auxiliary Configuration, Sub-menu Parameter Selection or Range of Setting