Configuration

Sub-menu

Parameter

Selection or Range

 

Parameter Definition

selection

 

of Setting

 

 

Relay 1

Frequency proportional output is a form of a process variable transmitter or control output

Relay 2

that pulses the relay as a pulse rate that is proportional to the input signal over a configured

Relay 3

relay range. The maximum frequency is set by the cycle time that is configurable between

Relay 4

0.1 and 999 seconds. The pulse duration is fixed and configured in seconds by an on time

Frequency

parameter.

 

 

 

 

 

 

 

Source

Any Analog Signal

 

PV Source

Proportional

 

 

See Table 6-3

 

 

Output Relay

 

 

 

 

 

 

 

High Range

-99999 to 99999

The high range is the PV based engineering unit

 

 

 

default = 100.00

value configured as the value that will produce a

 

 

 

100 percent (Maximum Frequency) duty cycle.

 

 

 

 

 

Low Range

-99999 to 99999

The low range is the PV based engineering unit

 

 

default = 0.00

value configured as the value that will produce a

 

 

 

0 percent (always inactive) duty cycle.

 

 

 

 

 

 

Invert

Enable

 

Inverts the proportional range of the applied

 

 

Disable (default)

 

analog input such that inverse relay operation is

 

 

 

 

achieved.

 

 

 

 

 

Cycle Time

0 to 999

Sets the Cycle Time of the maximum output

 

 

default = 10

frequency.

 

 

 

Max Freq=1/Cycle Time

 

 

 

Freq Output = Max Freq * (% Input/100)

 

 

 

For example:

 

 

 

Freq Output (100%)=Max Freq * 1

 

 

 

Freq Ouput (50%)= Max Freq * .5

 

 

 

Freq Ouput (25%)=Max Freq * .25

 

 

 

 

 

 

On Time

0.0 to 999

 

Sets the pulse duration. This value should be

 

 

default = 5

 

less than the cycle time for proper operation.

 

 

 

 

Typically this value is used to control the pulse

 

 

 

 

duration for the finial output control element.

 

 

 

 

 