Accessing Alarms Menu

Press Setup to display the Main menu.

Use the keys to select “Alarms” then press Enter to enter the sub-menu.

Press

to highlight the desired menu selection then press Enter to display the

 

group of parameters.

 

 

Refer to “Section 6.4.1 – “General Rules for Editing”.

 

 

 

Table 6-8 Alarms Configuration

 

 

 

 

 

Sub-menu

 

Parameter

Selection or

Parameter Definition

selection

 

 

 

Range of Setting

 

Alarm 1

 

Source

 

Any Analog Signal

Process Variable Source – Process Variable to be

Alarm 2

 

 

 

See Table 6-3

monitored by the alarm.

Alarm 3

 

Disable

 

Any Digital Signal

Select any Digital signal to disable the Alarm

Alarm 4

 

 

 

 

 

See Table 6-4

 

 

 

 

 

 

 

 

 

Type

 

High (default)

Alarm actions may be High or Low.

 

 

 

 

Low

 

 

 

 

 

 

 

 

Setpoint Value

-99999 to 99999.9

Setpoint value in engineering units

 

 

 

 

in Engineering

 

 

 

 

 

Units

 

 

 

 

 

default = 0.000

 

 

 

 

 

 

 

 

 

Latch

 

Disable (default)

When enabled, the alarm is latch ON until

 

 

 

 

Enable

acknowledged from the Alarm Status display.

 

 

 

 

 

 

 

Hysteresis

0.0 to 99999.9 in

Hysteresis - A user-specified hysteresis value in

 

 

 

 

engineering units

the engineering units of the process variable

 

 

 

 

default = 0.000

source is provided. Hysteresis in engineering

 

 

 

 

 

units can be set from 0 to the input span of the

 

 

 

 

 

monitored variable.

 

 

 

 

 

 

 

On Delay

0 to 120 seconds

An on-delay time value up to 120 seconds is

 

 

 

 

default = 0.000

available to prevent momentary alarm actions.

 

 

 

 

 

Number of seconds the alarm is active before

 

 

 

 

 

activating the Output.

 

 

 

 

 

 

82

UDA2182 Universal Dual Analyzer Product Manual

January 2009