Configuration

6.14 PID Control Configuration

Overview

PID (Option) - Proportional (P), Integral (I) and Derivative (D), (3-mode) control action based on the deviation or error signal created by the difference between the setpoint (SP) and the Process variable analog input value (PV). PID Tuning parameters are available.

Automatic tuning with Fuzzy Logic Overshoot Suppression can be configured.

Other parameters listed in this group deal with how the analyzer will control the process including: PV High and Low, Setpoint High and Low limits, the Control Algorithm and Action, PID Tracking (TRV and TRC), Number of Tuning Parameter Sets and associated parameters, Setpoint Rate, Power-up Recall, Output Limits, Failsafe Output Value, Alarm setpoint type and value, and Alarm Hysteresis.

PID Tracking

PID tracking is a means to control a PID’s output without the PID loop winding up. It is accomplished by the use of two inputs.

TRC (tracking control) – selects the tracking mode (See Table 6-13)

TRV (tracking value) – is the commanded output value in percentage (PID Output = TRV Input when TRC = ON) (See Table 6-13)

When TRC is active, the front-panel display will indicate TRV for the PID loop.

Remote PID Tracking

Variables can be connected to TRC and TRV to allow remote control of the PID output. TRC can be connected to a digital variable

TRV can be connected to an analog variable

PID Tracking versus Manual Mode

Tracking is not the same as manual mode.

Tracking value cannot be adjusted from the front-panel. Manual output value can.

Manual output cannot be adjusted remotely. Tracking value can.

Manual has priority over tracking. If operating in the tracking mode, the output can be adjusted from the front-panel by selecting manual and adjusting the output. When manual is terminated, the active mode will be TRC and the output will go to TRV.

Using Auto/Manual Switch

It may be desirable to use a discrete input to place a PID into manual momentarily to freeze the output. With tracking, this can be done.

1.Connect the TRV to PID output

2.Connect the TRC to a discrete input

When the discrete input is active, the output is frozen – MANUAL select.

When the discrete input is inactive, the PID runs in the auto mode – AUTO select.

92

UDA2182 Universal Dual Analyzer Product Manual

January 2009

Page 104
Image 104
Honeywell UDA2182 manual PID Control Configuration, Remote PID Tracking, PID Tracking versus Manual Mode