Outputs Calibration

Step

 

Action

 

 

Screen

12

 

 

 

 

 

 

Use

to select

 

OUTPUT 1

 

 

 

20mA Offset

-147

 

 

” 4 mA Offset” and repeat the

 

 

 

 

4mA Offset

3

 

 

process.

 

 

Reset 20mA Offs

 

 

 

 

 

Reset 4mA Offs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13Press “Enter” to store the 4mA Offset value.

Press “Exit” to cancel. The previous value is retained.

14If the calibration is suspect, you can reset the 20mA and 4mA Offset and calibrate again.

To calibrate additional Outputs, repeat the above steps Including powering down the unit before changing the connections to the output terminals.

When output calibration has been completed, re-install the field wiring removed in step 5. Disconnect power before opening

the case.

Close the case and power up the unit. Do not apply power until

the case is closed.

January 2009

UDA2182 Universal Dual Analyzer Product Manual

183