Configuration

 

 

 

 

 

 

Sub-menu

Parameter

Selection or Range

 

Parameter Definition

selection

 

of Setting

 

 

 

Relay 1

On / Off output relay turns On when the input is greater than the relay high and low ranges

Relay 2

and turns off when the input is less than the relay high and low ranges. This allows an on /

Relay 3

off control action with an adjustable dead band. The On state is controlled by a cycle time

Relay 4

and on duration parameters such to achieve a selectable output proportion. An invert

ON/OFF

parameter is available to allow inverse action such that the relay will cycle ON when below

the low range limit.

 

 

 

 

Control Relay

 

 

 

 

 

Source

Any Analog Signal

 

PV Source

 

 

 

 

See Table 6-3

 

 

 

 

 

 

 

 

 

High Range

-99999 to 99999

 

The high range is the PV based engineering unit

 

 

default = 100.00

 

value configured as the value that will produce a

 

 

 

 

100 percent (Maximum Frequency) duty cycle.

 

 

 

 

 

 

Low Range

-99999 to 99999

 

The low range is the PV based engineering unit

 

 

default = 0.00

 

value configured as the value that will produce a

 

 

 

 

0 percent (always inactive) duty cycle.

 

 

 

 

 

 

Invert

Enable

 

Inverts the proportional range or input state of

 

 

Disable (default)

 

the applied digital or analog input such that

 

 

 

 

inverse relay operation is achieved.

 

 

 

 

 

 

Cycle Time

0 to 999

 

Cycle time is that time period, in seconds,

 

 

default = 10

 

between relay activations.

 

 

 

 

 

 

On Time

0,0 to 999

 

Sets the pulse duration. This value should be

 

 

default = 5

 

less than the cycle time for proper operation.

 

 

 

 

Typically this value is used to control the pulse

 

 

 

 

duration for the finial output control element.

 

 

 

 

 

 

January 2009

UDA2182 Universal Dual Analyzer Product Manual

79

Page 91
Image 91
Honeywell UDA2182 manual On/Off