Honeywell UDA2182 manual Pulse Output

Models: UDA2182

1 258
Download 258 pages 46.92 Kb
Page 92
Image 92

Configuration

Sub-menu

Parameter

Selection or Range

 

Parameter Definition

selection

 

of Setting

 

 

Relay 1

Pulse Output relay will provide a fixed duty cycle when the applied input signal is ON. The

Relay 2

cycle time and pulse duration are configurable parameters. The relay will be OFF when the

Relay 3

applied input is OFF. An inverse parameter allows the input to be inverted for reverse

Relay 4

behavior.

 

 

 

Pulse Output

Source

Any Digital Signal

 

PV Source

 

See Table 6-4

 

 

Control Relay

 

 

 

 

Invert

Enable

 

The digital output relays "invert" parameter can

 

 

 

 

Disable (default)

 

be used to allow direct (invert disabled) or

 

 

 

 

reverse (invert enabled) control actuation.

 

 

 

 

 

 

Cycle Time

0 to 999

 

Cycle time is that time period, in seconds,

 

 

default = 10.0

 

between relay activations.

 

 

 

 

 

 

On Time

0 to 999

 

The time in seconds that the relay is On during each

 

 

default = 5.0

 

cycle when the input to the Pulse Output is ON. When

 

 

 

 

the Input to the Pulse output is OFF the relay is not

 

 

 

 

activated.

 

 

 

 

 

80

UDA2182 Universal Dual Analyzer Product Manual

January 2009

Page 92
Image 92
Honeywell UDA2182 manual Pulse Output