Chapter 4 Provisioning Using ASH and SNMP

Set Alarm Thresholds

F I N A L D R A F T - C I S C O C O N F I D E N T I A L

Table 4-1 Alarm Threshold Attribute Definitions (continued)

 

 

 

 

 

Variable

 

Maximum

 

 

 

 

 

 

 

Attribute

Definition

Syntax

Access

Description

 

 

 

 

 

 

 

 

 

 

 

 

 

 

cerent15216Edfa

Loss of

Integer

Read-write

Used to set the amount the input signal

 

 

 

 

LOSHysteresis

signal

(0 to 1000,

 

must increase above the LOS Threshold

 

 

 

 

 

(input

100

 

level before the alarm is cleared. This

 

 

 

 

 

power)

default)

 

attribute, in conjunction with the loss of

 

 

 

 

 

hysteresis

 

 

input signal alarm threshold, enables

 

 

 

 

 

 

 

 

efficient clearing of alarms. Set this

 

 

 

 

 

 

 

 

attribute at a value that is appropriate for

 

 

 

 

 

 

 

 

the application so that the alarm

 

 

 

 

 

 

 

 

condition will clear when input is stable.

 

 

 

 

 

 

 

 

Consult with the Cisco TAC to determine

 

 

 

 

 

 

 

 

the correct value for your application. As

 

 

 

 

 

 

 

 

a guideline, Cisco recommends setting

 

 

 

 

 

 

 

 

the value 1 dB above the LOS Threshold

 

 

 

 

 

 

 

 

value. With this setting, the module will

 

 

 

 

 

 

 

 

clear the alarm if it detects a signal level

 

 

 

 

 

 

 

 

of 1 dB above the current LOS Threshold

 

 

 

 

 

 

 

 

value. Valid entries are between 0 and

 

 

 

 

 

 

 

 

1000 and are in dB times 100. For

 

 

 

 

 

 

 

 

example, if the hysteresis required is 1

 

 

 

 

 

 

 

 

dB, the power alarm hysteresis is 100.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

cerent15216Edfa

Minimum

Integer

Read-write

Alarm notifies operations personnel if

 

 

 

 

CtmpMin

case

(–10 to 10,

 

the case temperature of the

 

 

 

 

 

temperature

–5 default)

 

ONS 15216 EDFA2 drops below a level

 

 

 

 

 

 

 

 

that impacts proper operation of the

 

 

 

 

 

 

 

 

optical network. The minimum case

 

 

 

 

 

 

 

 

temperature should be set at a value that

 

 

 

 

 

 

 

 

is appropriate for the intended

 

 

 

 

 

 

 

 

application and within product

 

 

 

 

 

 

 

 

specifications. Consult with the Cisco

 

 

 

 

 

 

 

 

TAC to determine the correct value for

 

 

 

 

 

 

 

 

your application. As a guideline, Cisco

 

 

 

 

 

 

 

 

recommends that minimum case

 

 

 

 

 

 

 

 

temperature be set at 1°C. Valid entries

 

 

 

 

 

 

 

 

are between –10 and 10°C.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

cerent15216Edfa

Minimum

Integer

Read-write

Used to set the amount that the case

 

 

 

 

CtmpMinHystere

case

(0 to 10,

 

temperature of the module must rise

 

 

 

 

sis

temperature

1 default)

 

above the minimum case temperature

 

 

 

 

 

hysteresis

 

 

alarm level before the alarm is cleared.

 

 

 

 

 

 

 

 

Set the hysteresis at a value that is

 

 

 

 

 

 

 

 

appropriate for the application so that the

 

 

 

 

 

 

 

 

alarm condition clears when the input is

 

 

 

 

 

 

 

 

stable. Consult with the Cisco TAC to

 

 

 

 

 

 

 

 

determine the correct value for your

 

 

 

 

 

 

 

 

application. As a guideline, Cisco

 

 

 

 

 

 

 

 

recommends that the hysteresis value be

 

 

 

 

 

 

 

 

set at 1°C. Valid entries are between 0

 

 

 

 

 

 

 

 

and 10°C. Setting this value to 0 disables

 

 

 

 

 

 

 

 

this option.

 

 

 

 

 

 

 

 

 

 

 

 

 

 