Siemens 6RA70 specifications Fault Description

Models: 6RA70

1 232
Download 232 pages 59.99 Kb
Page 102
Image 102

Fault

No.

 

Description

 

 

 

Cause as a function of fault value

 

 

Further information (r047.002 to r047.016)

 

 

(r047.001, r949.001 or r949.009 with acknowledged error)

 

 

 

 

 

 

 

 

 

 

F043 EMF too high for braking operation (active in operating states of – –, I, II)

This fault message is activated if the following 5 conditions are fulfilled when a torque direction reversal is requested (selection of MI or MII):

P272=0 (fault message is parameterized and not alarm + field weakening)

A parameterized, additional, torque-free interval (P160 0) has expired

Parallel drive is ready for engagement of the new torque direction

The absolute value of the armature current (K0118) requested in the new torque direction is >0.5% of P072

The calculated firing angle (K0101) for the armature current requested for the new torque direction is >165 degrees.

Possible fault causes

No “speed-dependent field weakening" (P081=0) is parameterized even though operation in the field weakening range is needed for the requested maximum speed

Note:

In motor operation, it is possible to reach EMF values corresponding to the peak of the phase-to-phase supply voltage at a firing angle of αG=30° (rectifier stability limit P150) and low armature currents.

Setpoint EMF for field weakening operation too high (parameter P101 is set too high)

Supply voltage dip

EMF controller or field current controller is not optimized, possibly resulting in excessive EMF on power-up.

 

Fault value:

r047 Index 002 to 016:

 

 

 

 

 

Calculated firing angle (armature) before limitation (K0101)

i002

Instantaneously measured actual EMF (K0287)

 

 

i003

Armature current controller setpoint (K0118)

 

 

 

 

F044 A slave connected to the paralleling interface is not operating

(active when U800 = 1 or 2 and U806>10 (master) after receipt of the first valid protocol in operating states – –, I, II)

Fault value:

1A fault message is active on a slave

2A slave is not in operation (e.g. because its enable input is set to "0")

F046 Analog select input for main setpoint (terminals 4 and 5) faulty (active in operating states of o6)

This fault message is activated when P700=2 (current input 4 to 20 mA) and an input current of less than 2mA is flowing.

Possible fault causes

Open circuit in supply cable

P700 is incorrectly set

F047 Analog select input 1 (terminals 6 and 7) is faulty (active in operating states of o6)

This fault message is activated when P710=2 (current input 4 to 20 mA) and an input current of less than 2mA is flowing.

Possible fault causes

Open circuit in supply cable

P710 is incorrectly set

Siemens Energy & Automation

9-13

SIMOREG DC Master Base Drive Panel

Operating Instructions

Page 102
Image 102
Siemens 6RA70 specifications Fault Description