Siemens 6RA70 specifications 10-79, See Change Access / Status P786 USS bus address for G-SST1

Models: 6RA70

1 232
Download 232 pages 59.99 Kb
Page 200
Image 200

PNU

Description

Value range [Unit] Steps

No. indices Factory setting Type

See Change (Access / Status)

P786

USS bus address for G-SST1

*

This parameter is functional only when P780=2 (USS protocol). Address via

(G170)

which the unit can be addressed in USS bus operation.

 

 

 

P787

Telegram failure time for G-SST1

 

The failure time set in this parameter is valid when setting P780=2 (USS

(G170)

protocol) is selected.

 

0.000

No time monitoring

 

0.001...65.000 Time which may elapse between the receipt of two

 

 

telegrams addressed to the unit before a fault message

 

 

is activated.

 

Fault message F011 is activated if no valid telegram is received within this

 

time period.

 

Note:

The telegram monitoring function is active

from the receipt of the first error-free telegram after connection of the electronics power supply

from the receipt of the first error-free telegram after the telegram monitor has responded (i.e. monitoring timeout).

P788

Source for activation of F011

*

Selection of binector which will activate fault message F011 when it

(G170)

switches to log. "1"

 

 

2030 = binector B2030

 

2031 = binector B2031

 

 

r789

Diagnostic information for G-SST1

(G170)

Free-running counter, overflow at 65535

i001:

Number of error-free telegrams

 

 

i002:

Number of errored telegrams:

 

 

Byte frame, parity, overrun or BCC error

 

i003:

Number of byte frame errors

 

i004:

Number of overrun errors

 

i005:

Parity error

 

i006:

STX error:

 

 

Start interval before STX not observed,

 

 

telegram residual transfer time not observed,

 

 

delay time of LGE character too long,

 

 

erroneous STX, i.e. 02

 

i007:

Violation of telegram residual transfer time

 

i008:

Block check error

 

i009:

Incorrect telegram length:

 

 

With P782=3 or 4 only:

 

 

The length of the received telegram is P781 + P782

 

 

(Note: If the received values are correct, they will be processed

 

 

even when this error has been detected)

 

i010:

Timeout error:

 

 

No valid telegram has been received for a period exceeding the

 

 

setting in P787. After the occurrence of a timeout error, this

 

 

counter is not activated again until the next valid telegram is

 

 

received.

0 to 30

1

0.000 to 65.000 [s]

0.001s

2030, 2031

Ind: None

P052

= 3

FS=0

P051

= 40

Type: O2

Offline

 

 

 

Ind: None

P052

= 3

FS=0.000

P051

= 40

Type: O2

Offline

Ind: None

P052

= 3

FS=2030

P051

= 40

Type: L2

Offline

 

 

 

Ind: 10

P052

= 3

Type: O2

 

 

G-SST 2 (RS485 on X172) (see also Section 8, Sheets G171 and G173 and Section 9 of Operating Instructions 6RX1700-0AD**)

P790

Selection of protocol for G-SST2 basic converter interface

0, 2, 5, 9

Ind: None

P052

= 3

*

0

Setting has no function

1

FS=0

P051

= 40

(G171)

 

Type: O2

Offline

2

USS protocol

 

(G173)

 

 

 

 

5

”Peer-to-peer” communication

 

 

 

 

 

 

 

 

 

 

9

For internal factory test purposes

 

 

 

 

 

 

 

 

 

 

 

SIEMENS Energy & Automation

10-79

SIMOREG DC Master Base Drive Panel Operating Instructions

 

Page 200
Image 200