11-12

1

2

3

4

5

6

7

8

6RA70 DC MASTER

SIMPLIFIED BLOCK DIAGRAM

(ALL AVAILABLE FUNCTIONS ARE NOT SHOWN ON SIMPLIFIED BLOCK DIAGRAM)

Control word 2

Sheet 11 Control

When P649 = 9, bit-serial input of control bits (P676 to P691 are effective)

When P649 <> 9, word-serial input of control bits (P676 to P691 are not effective)

r651

31 30 29 28 27 26 25 Bit24

Siemens Energy & SIMOREG DC Master Base Drive Panel Operating

P649.B (9)

K

P676.B (0)

B

P677.B (0)

B

P680.B (0)

B

P681.B (0)

B

P684.B (1)

B

P685.B (1)

B

P686.B (1)

B

P687.B (0)

B

P688.B (1)

B

P689.B (1)

B

P690 (0)

B

P691.B (1)

B

Bit No.

Meaning

Bit 16

Select function data set bit 0

Bit 17

Select function data set bit 1

Bit 18

Spare

Bit 19

Spare

Bit 20

Select fixed setpoint 1

Bit 21

Select fixed setpoint 2

Bit 22

Spare

Bit 23

Spare

Bit 24

1=Enable speed controller droop

 

0=Speed controller droop disabled

Bit 25

1=Enable speed controller

 

0=Speed controller disabled

Bit 26

0=External fault 2

 

1=No external fault 2

Bit 27

0=Master drive (speed control)

 

1=Slave drive (torque control)

Bit 28

0=External alarm 1

 

1=No external alarm 1

Bit 29

0=External alarm 2

 

1=No external alarm 2

Bit 30

0=Select Bico data set 1

 

1=Select Bico data set 2

Bit 31

Main contactor check-back signal

Control word 2

K0031

to sheet "Fixed setpoint" [ 2.3 ]

to sheet "Fixed setpoint" [ 2.3 ]

to sheet "Speed controller"

[ 3.4 ]

to sheet "Speed controller"

[ 3.4 ]

23 22 21 20 19 18 17 Bit16

Display of control word 2 (r651)

on 7-segment display

OR'd WITH P430.01

OR'd WITH P430.02

P360.02 (0ms) (0...10000ms)

External fault 2

1 = "Fault F022"

P360.03 (0ms) (0...10000ms)

External alarm 1

1 = "Alarm A021"

P360.04 (0ms) (0...10000ms)

External alarm 2

1 = "Alarm A022"

Word 2

Instructions

Automation

11

Page 227
Image 227
Siemens 6RA70 specifications 11-12, Sheet 11 Control