PNU

 

Description

 

 

Value range

No. indices

See

 

 

 

 

 

 

 

[Unit]

Factory

Change

 

 

 

 

 

 

 

Steps

setting

(Access /

 

 

 

 

 

 

 

 

Type

Status)

 

P807

 

Telegram failure time for G-SST3

 

0.000 to 65.000

Ind: None

P052 = 3

 

 

 

The failure time set in this parameter is valid when setting P800=2 (USS

 

[s]

FS=0.000

P051 = 40

 

(G172)

 

 

0.001s

Type: O2

Offline

 

 

protocol) or P800=5 (peer-to-peer) is selected.

 

 

 

 

 

 

 

 

(G174)

0.000

No time monitoring

 

 

 

 

 

 

 

 

 

 

 

 

 

0.001...65.000 Time which may elapse between the receipt of two

 

 

 

 

 

 

 

 

telegrams addressed to the unit before a fault message

 

 

 

 

 

 

 

 

is activated.

 

 

 

 

 

 

 

 

Fault message F013 is activated if no valid telegram is received within this

 

 

 

 

 

 

 

time period.

 

 

 

 

 

 

 

 

Note:

 

 

 

 

 

 

 

 

 

The telegram monitoring function is active

 

 

 

 

 

 

 

from the receipt of the first error-free telegram after connection of the

 

 

 

 

 

 

 

electronics power supply

 

 

 

 

 

 

 

 

from the receipt of the first error-free telegram after the telegram monitor

 

 

 

 

 

 

 

has responded (i.e. monitoring timeout).

 

 

 

 

 

 

 

Since the telegram transfer time is dependent on the set baud rate, the

 

 

 

 

 

 

 

following minimum setting values for P807 are recommended:

 

 

 

 

 

 

 

Baud rate as set in P803:

Recommended minimum value for P807:

 

 

 

 

 

 

300

baud

0.520s

 

 

 

 

 

 

600

baud

0.260s

 

 

 

 

 

 

1200

baud

0.140s

 

 

 

 

 

 

2400

baud

0.080s

 

 

 

 

 

 

 

4800

baud

0.040s

 

 

 

 

 

 

 

Note:

 

 

 

 

 

 

 

 

 

If the "Automatic restart" function is selected (P086>0) on the peer-to-peer

 

 

 

 

 

 

 

communication partner, then only a parameter setting of P807>P086 (on the

 

 

 

 

 

 

 

communication partner) is meaningful.

 

 

 

 

 

 

 

 

 

 

 

 

 

P808

 

Source for activation of F013

 

9030, 9031

Ind: None

P052 = 3

*

 

Selection of binector which will activate fault message F013 when it

 

 

FS=9030

P051 = 40

 

(G172)

 

 

 

Type: L2

Offline

 

 

switches to log. "1"

 

 

 

 

(G174)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9030 = binector B9030

 

 

 

 

 

 

 

 

9031 = binector B9031

 

 

 

 

 

 

 

 

 

 

 

 

 

 

r809

 

Diagnostic information for G-SST3

 

 

Ind: 10

P052 = 3

 

 

 

Free-running counter, overflow at 65535

 

 

Type: O2

 

 

(G172)

 

 

 

 

 

 

 

 

Number of error-free telegrams

 

 

 

 

 

(G174)

 

i001:

 

 

 

 

 

 

 

i002:

Number of errored telegrams:

 

 

 

 

 

 

 

 

Byte frame, parity, overrun or BCC error

 

 

 

 

 

 

 

i003:

Number of byte frame errors

 

 

 

 

 

 

 

i004:

Number of overrun errors

 

 

 

 

 

 

 

i005:

Parity error

 

 

 

 

 

 

 

 

i006:

STX error:

 

 

 

 

 

 

 

 

 

Start interval before STX not observed,

 

 

 

 

 

 

 

 

telegram residual transfer time not observed,

 

 

 

 

 

 

 

 

delay time of LGE character too long,

 

 

 

 

 

 

 

 

erroneous STX, i.e. 02

 

 

 

 

 

 

 

i007:

Violation of telegram residual transfer time (USS prot. only)

 

 

 

 

 

 

 

i008:

Block check error

 

 

 

 

 

 

 

 

i009:

Incorrect telegram length:

 

 

 

 

 

 

 

 

With PP802=3 or 4 only:

 

 

 

 

 

 

 

 

The length of the received telegram is P801 + P802

 

 

 

 

 

 

 

 

(Note: If the received values are correct, they will be processed

 

 

 

 

 

 

 

 

even when this error has been detected)

 

 

 

 

 

 

 

i010:

Timeout error:

 

 

 

 

 

 

 

 

 

No valid telegram has been received for a period exceeding the

 

 

 

 

 

 

 

 

setting in P807. After the occurrence of a timeout error, this

 

 

 

 

 

 

 

 

counter is not activated again until the next valid telegram is

 

 

 

 

 

 

 

 

received.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10-84

SIEMENS Energy & Automation

 

SIMOREG DC Master Base Drive Panel Operating Instructions

Page 205
Image 205
Siemens 6RA70 specifications 10-84, P808, R809 Diagnostic information for G-SST3