Siemens 6RA70 specifications 10-47

Models: 6RA70

1 232
Download 232 pages 59.99 Kb
Page 168
Image 168

PNU

Description

Value range [Unit] Steps

No. indices Factory setting Type

See Change (Access / Status)

P431

Source for fixed setpoint

*

Selection of connector to be injected as the fixed setpoint

 

(G127)

0 = connector K0000

 

1 = connector K0001

 

etc.

P432

Source for selection of ramp-function generator bypass

*

Selection as to whether or not ramp-function generator must be bypassed

 

(G127)

when the fixed setpoint is injected.

The ramp-function generator is bypassed if the AND operation between the

 

 

binector selected via an index of P430 and the setting in the same index of

 

P432 produces a log. "1"

P433

Source for standard setpoint

*

Selection of the connector to be applied if fixed-setpoint injection is not

FDS

selected

 

(G127)

0 = connector K0000

 

1 = connector K0001

 

etc.

All connector numbers

1

0 to 1

1

All connector numbers

1

Ind: 8

P052

= 3

FS=0

P051

= 40

Type: L2

Offline

 

 

 

Ind: 8

P052

= 3

FS=0

P051

= 40

Type: O2

Offline

 

 

 

Ind: 4

P052

= 3

FS=11

P051

= 40

Type: L2

Offline

 

 

 

Inching setpoint

Function: Up to 8 connectors can be selected in P436 indices .01 to .08. These can be applied as an inching setpoint (K0202, K0207) via the binectors selected in P435, indices .01 to .08 (setpoint is applied when binector switches to log. "1" state). P437 indices .01 to .08 can be set to define for each setpoint individually whether the ramp-function generator must be bypassed on setpoint injection. If more than one inching setpoint is injected, an output value corresponding to inching setpoint = 0% is applied.

If inching setpoint injection is not selected, the connector set in P438 is applied to K0207.

P435

Source for injection of inching setpoint

All binector numbers

Ind: 8

P052

= 3

*

Selection of binector to control injection of the inching setpoint

1

FS=0

P051

= 40

 

 

Type: L2

Offline

(G129)

("1" state = inching setpoint injected).

 

 

 

 

 

 

 

 

 

 

 

0 = binector B0000

 

 

 

 

 

1 = binector B0001

 

 

 

 

 

etc.

 

 

 

 

 

 

All connector

 

 

 

P436

Source for inching setpoint

Ind: 8

P052

= 3

*

Selection of connector to be injected as the inching setpoint

numbers

FS=0

P051

= 40

 

1

Type: L2

Offline

(G129)

 

0 = connector K0000

 

 

 

 

 

1 = connector K0001

 

 

 

 

 

etc.

 

 

 

 

 

 

0 to 1

 

 

 

P437

Source for selection of ramp-function generator bypass

Ind: 8

P052

= 3

*

Selection as to whether or not ramp-function generator must be bypassed

1

FS=0

P051

= 40

 

 

Type: O2

Offline

(G129)

when the inching setpoint is injected.

 

 

 

 

 

The ramp-function generator is bypassed if the AND operation between the

 

 

 

 

 

 

 

 

 

 

binector selected via an index of P435 and the setting in the same index of

 

 

 

 

 

P437 produces a log. "1".

 

 

 

 

 

 

All connector

 

 

 

P438

Source for standard setpoint

Ind: 4

P052

= 3

*

Selection of the connector to be applied if inching-setpoint injection is not

numbers

FS=208

P051

= 40

FDS

1

Type: L2

Offline

selected

 

 

 

 

 

 

 

 

 

(G129)

0 = connector K0000

 

 

 

 

 

1 = connector K0001

 

 

 

 

 

etc.

 

 

 

 

 

 

 

 

 

 

Crawling setpoint

Function: Up to 8 connectors can be selected in P441 indices .01 to .08. These can be applied as an additional crawling setpoint (K0201, K0206) via the binectors selected in P440, indices .01 to .08. P445 can be set to define whether the setpoint must be applied when the selected binectors have reached the log. "1" state (when P445=0) or in response to a 0 1 transition (when P445=1). When setpoint injection in response to a 0 1 transition is selected, the setpoint injection function is reset when the binector selected in P444 switches to the log. "0" state. P442 indices .01 to .08 can be set to define for each setpoint individually whether the ramp-function generator must be bypassed on setpoint injection.

If crawling setpoint injection is not selected, the connector set in P443 is applied to K0206.

P440

Source for injection of crawling setpoint

All binector numbers

Ind: 8

P052

= 3

*

Selection of binector to control injection of the crawling setpoint.

1

FS=0

P051

= 40

 

 

Type: L2

Offline

(G130)

 

 

0 = binector B0000

 

 

 

 

 

1 = binector B0001

 

 

 

 

 

etc.

 

 

 

 

 

 

 

 

 

 

SIEMENS Energy & Automation

10-47

SIMOREG DC Master Base Drive Panel Operating Instructions

 

Page 168
Image 168
Siemens 6RA70 specifications 10-47