P092

Delay times for field reversal

(G200)

These times are used to control a reversing contactor for reversing the field

polarity on a 1-quadrant converter with field reversal.

 

 

i001:

Delay time for the field reduction before opening of the current

 

 

field contactor

 

 

When field polarity reversal is initiated, the delay time set in

 

 

P092.i001 elapsed after reaching Ifield (K0265) < Ifield min

 

 

(P394) before the current field contactor is opened.

 

i002:

Delay time before actuation of the new field contactor

 

 

[only SW 1.7 and later]

 

 

After opening the current field contactor the delay time set in

 

 

P092.i002 elapsed before the field contactor for the "new" field

 

 

direction is actuated (drop-out delay time of the contactor use is

 

 

usually longer then the pick-up delay time).

 

i003:

Delay time for enabling the field firing pulses

 

 

[only SW 1.7 and later]

 

 

After actuation of the field contactor for the "new" field direction,

 

 

the delay time acc. to P092.i003 elapses before the field firing

 

 

pulses are enabled. This time must be longer than the pick-up

 

 

delay time of the contactor used.

 

i004:

Delay time after the field build-up before armature enable

 

 

[only SW 1.7 and later]

 

 

After - directly following the field firing pulse enable - the actual

 

 

field current value Ifield in the "new" field direction has reached

 

 

the value Ifield (K0265) > Ifield set (K0268)*P398/100%, the

 

 

delay time acc. to P092.i004 elapses. Then the internal

 

 

(armature) "Operating enable of field reversal" is issued, i.e. the

 

 

Stopping of the drive in operating state o1.4 is canceled. This

 

 

delay time permits waiting of the end of overshooting of the

 

 

actual field current value and therefore overshooting of the EMF

 

 

of the DC machine straight after the field current has been built

 

 

up again, before the "armature operating enable" is issued. This

 

 

is intended to prevent armature overcurrents due to excessive

 

 

EMF during overshooting.

P093

Pick-up delay for line contactor

 

 

Pick-up of the line contactor is delayed in relation to "Switch on auxiliaries"

 

by the time delay set in this parameter.

 

 

 

 

P094

Switch-off delay for auxiliaries

 

 

Switch-off of the auxiliaries is delayed in relation to dropout of the line

 

contactor by the time delay set in this parameter.

 

 

 

 

P095

Pick-up time for a contactor in the DC circuit

 

 

If the DC output (terminals 1C1 and 1D1) is switched through to the motor

 

via a contactor, and if this contactor is controlled by the "Relay for line

 

contactor" (terminals 109 and 110), then the gating pulses may not be

 

enabled until the contactor has safely picked up. For this purpose, it may be

 

necessary to parameterize an additional delay time for the pick-up

 

operation. The timer set in P095 commences during a pick-up operation

 

when the converter reaches operating state o5. If the timer has still not run

 

down by the time the converter exits state o4, then the converter dwells in

 

state o3.2 until the timer has finished.

 

 

During the time period set in P095, the "Main contactor checkback" signal

 

must also switch to "1" if this function is activated (see P691). Otherwise the

 

converter dwells in state o3.3 until the timer has finished and fault message

 

F004 is then output with fault value 6.

 

 

 

 

P096

After-running time for the device fan

[SW 1.6 and later]

After the drive has been shut down (operating state 7.0 reached)

the device fan continues to run until the power section has cooled down.

With this parameter you can set the minimum duration for the after-running time.

Note:

If the field current is not switched off after the drive is shut down (see P082), the field current can prevent cooling of the power section. In this case, the equipment blower is never switched off.

0.0to 10.0

[s]

0.1s

0.0to 120.0

[s]

0.1s

0.0to 6500.0

[s]

0.1s

0.00to 1.00

[s]

0.01s

0.0to 60.0 [min] 0.1min

Ind: 4

P052

= 3

FS=

P051

= 40

i001: 3.0

Online

i002: 0.2

 

 

i003: 0.1

 

 

i004: 3.0

 

 

Type: O2

 

 

Ind: None

P052

= 3

FS=0.0

P051

= 40

Type: O2

Online

 

 

 

Ind: None

P052

= 3

FS=0.0

P051

= 40

Type: O2

Online

 

 

 

Ind: None

P052

= 3

FS=0.00

P051

= 40

Type: O2

Online

Ind: None

P052

= 3

FS=4.0

P051

= 40

Type: O2

on-line

SIEMENS Energy & Automation

10-21

SIMOREG DC Master Base Drive Panel Operating Instructions

 

Page 142
Image 142
Siemens 6RA70 specifications 10-21, P093 Pick-up delay for line contactor, P094 Switch-off delay for auxiliaries