Fault

 

 

Description

 

 

No.

 

Cause as a function of fault value

 

 

 

Further information (r047.002 to r047.016)

 

 

 

(r047.001, r949.001 or r949.009 with acknowledged error)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11 Checksum of non-volatile data (part 1)

 

 

i002

Calculate checksum

 

 

is not correct

 

 

i003 Checksum found in EEPROM

 

 

12 Checksum of non-volatile data (part 2)

 

 

 

 

 

 

 

 

 

 

 

is not correct

 

 

 

 

 

 

 

13 Checksum of non-volatile data (part 3)

 

 

 

 

 

 

 

is not correct

 

 

 

 

 

 

 

20 Checksum of configuring table of parameter values is not

 

 

 

 

 

correct

 

 

 

 

 

 

 

Possible fault causes

 

 

 

 

 

 

 

Defective EEPROM

 

 

 

 

 

 

 

“Restore to default value” has never been executed

 

 

 

 

 

with this software (e.g. after software replacement)

 

 

 

 

 

Possible remedy:

 

 

 

 

 

 

 

Acknowledge fault, execute “Restore to default value”

 

 

 

 

 

and start up the drive again! Check interference

 

 

 

 

 

 

 

suppression measures and improve if necessary.

 

 

 

 

 

 

 

 

F063

Errors in compensation data of analog inputs and outputs

 

 

 

 

 

(active in all operating states)

 

 

 

 

 

 

 

This function monitors whether the factory-set compensation data for the analog inputs and outputs are plausible

 

 

Possible fault cause:

 

 

 

 

 

 

 

Defective A7001 or A7006 electronics board

 

 

 

 

 

 

 

Fault value:

 

r047 Index 002 to 016:

 

 

 

 

 

 

 

 

11 Incorrect number of words in compensation values

 

 

i002 Incorrect number of words

 

 

for analog inputs and outputs of A7001

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12 Checksum error in compensation values for

 

 

i002

Calculated checksum

 

 

analog inputs and outputs of A7001

 

 

i003

Errored checksum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13 Incorrect value among compensation values for

 

 

i002

Incorrect value

 

 

analog inputs and outputs of A7001

 

 

 

 

 

 

 

 

 

 

 

 

 

 

23 Incorrect value among compensation values for

 

 

i002

Incorrect value

 

 

analog inputs and outputs of A7006

 

 

 

 

 

 

 

 

 

 

 

 

F064

Watchdog timer has initiated a reset

 

 

 

 

 

 

 

(active in all operating states)

 

 

 

 

 

 

 

An internal microprocessor hardware counter monitors whether the program for calculating the firing pulses runs at least once

 

 

every 14 ms (program is executed on average every 2.7 to 3.3 ms). If this is not the case, the counter initiates a reset, F064 is

 

 

then displayed.

 

 

 

 

 

 

 

Possible fault causes

 

 

 

 

 

 

 

A7001 electronics board is defective

 

 

 

 

 

 

 

Excessive EMC-related interference is present (e.g. due to unprotected contactors, unscreened cables, loose shield

 

 

connections)

 

 

 

 

 

 

 

 

 

 

 

 

 

F065

 

Illegal microprocessor status

 

 

 

 

 

 

 

(active in all operating states)

 

 

 

 

 

 

 

An internal microprocessor hardware function monitors the microprocessor for illegal operating states.

 

 

Possible fault causes

 

 

 

 

 

 

 

A7001 electronics board is defective

 

 

 

 

 

 

 

Excessive EMC-related interference is present (e.g. due to unprotected contactors, unscreened cables, loose shield

 

 

connections)

 

 

 

 

 

 

 

 

 

 

 

 

F067

Converter cooling faulty

 

 

 

 

 

 

(active in operating states of o13)

 

 

 

 

 

 

The heatsink temperature monitoring function is activated 6s after connection of the electronics supply.

 

(The current heat sink temperature is indicated at parameter r013 and on connector K050)

 

 

 

 

 

 

 

 

9-24

 

 

 

 

 

Siemens Energy & Automation

 

 

 

 

 

SIMOREG DC Master Base Drive Panel Operating Instructions

Page 113
Image 113
Siemens 6RA70 specifications Fault, F063, F064 Watchdog timer has initiated a reset, F065 Illegal microprocessor status