P321

 

Multiplier for additional setpoint

-300.00 to 300.00

Ind: 4

P052

= 3

 

 

 

 

[%]

FS=100.00

P051

= 40

 

FDS

 

 

0.01%

Type: I2

Online

 

(G135)

 

 

 

 

 

 

 

P322

 

Source for multiplier for main setpoint

All connector

Ind: 4

P052

= 3

*

 

0 = Connector K0000

numbers

FS=1

P051

= 40

 

FDS

 

1

Type: L2

Offline

 

 

1 = Connector K0001

 

(G135)

 

 

 

 

 

 

 

etc.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P323

 

Source for multiplier for additional setpoint

All connector

Ind: 4

P052

= 3

*

 

0 = Connector K0000

numbers

FS=1

P051

= 40

 

FDS

 

1

Type: L2

Offline

 

 

1 = Connector K0001

 

 

 

 

 

 

 

(G135)

 

 

 

 

 

 

 

etc.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10.16 Ramp-function generator

P330

*

FDS (G136)

Factor for ramp-function generator times

[SW 2.1 and later]

Selection of a factor for the values set in parameters P296, P297, P298, P303 to P314 and P542 (ramp-function generator times).

0Factor = 1

1Factor = 60

i.e. effective ramp-function generator times = values set in [minutes] instead of in [seconds]

0 bis 1

1

Ind: 4

WE=0

Typ: O2

P052 = 3

P051 = 40 off-line

10.17 Setting values for monitoring functions and limits

Setting values for monitoring functions

 

 

 

 

 

 

-90 to 0

 

 

 

P351

Threshold for undervoltage trip

Ind: 4

P052 = 3

 

If the line voltage drops below a specific value (P078) and does not return to

[%]

 

FS=-20

P051 = 40

FDS

Armature:

 

Type: I2

Online

 

the permissible tolerance range within the "Restart time" set in P086, fault

1% of P078.001

 

 

 

 

message F006 is activated. The drive dwells in operating state o4 or o5

 

 

 

 

Field:

 

 

 

 

while the line undervoltage persists.

 

 

 

 

1% of P078.002

 

 

 

 

 

 

 

 

P352

Source for overvoltage trip

0 to 99

 

Ind: 4

P052 = 3

 

If the line voltage exceeds a specific value (P078) and does not return to the

[%]

 

FS=20

P051 = 40

FDS

Armature:

 

Type: O2

Online

 

permissible tolerance range within the "Restart time" set in P086, fault

1% of P078.001

 

 

 

 

message F007 is activated.

 

 

 

 

Field:

 

 

 

 

 

1% of P078.002

 

 

 

 

 

 

 

 

 

P353

Response threshold for phase failure monitoring

10 to 100

 

Ind: 4

P052 = 3

 

If the line voltage drops below the permissible value in operating states of

[%]

 

FS=40

P051 = 40

FDS

Armature:

 

Type: O2

Online

o4 and does not return to an "acceptable" value within the "Restart time"

 

 

1% of P078.001

 

 

 

 

set in P086, fault message F004 or F005 is activated.

Field:

 

 

 

 

The drive dwells in operating state o4 or o5 for the period that the line

1% of P078.002

 

 

 

 

voltage remains below the threshold and during the subsequent voltage

 

 

 

 

 

stabilization period set in P090.

 

 

 

 

 

When a switch-on command is entered, the converter dwells in operating

 

 

 

 

 

states o4 and o5 for a maximum total delay period for both states set in

 

 

 

 

 

P089 until the voltages in all phases exceed the threshold set in this

 

 

 

 

 

parameter before fault message F004 or F005 is activated.

 

 

 

 

 

 

 

 

 

 

P355

Stall protection time

0.0 to 600.0

 

Ind: 4

P052 = 3

 

F035 is activated if the conditions for the "Stall protection" fault message are

[s]

 

FS=0,5

P051 = 40

FDS

0.1s

 

Type: O2

Online

 

fulfilled for longer than the period set in P355.

 

 

 

 

 

When P355=0.0, the "Drive blocked" monitoring function (F035) is

 

 

 

 

 

deactivated and alarm A035 is likewise suppressed.

 

 

 

 

 

 

 

 

 

 

P357

Threshold for tachometer interruption monitoring

10 to 70

 

Ind: 4

P052 = 3

 

F042 is suppressed if the actual EMF value is lower than the value set in

[%]

 

FS=10

P051 = 40

FDS

1%

 

Type: O2

Online

P357.

 

 

 

 

 

 

 

The setting is entered as a % of the ideal mean DC voltage value at α=0,

 

 

 

 

 

i.e. as a % of P078.001 * 1.35

 

 

 

 

10-42

 

 

SIEMENS Energy & Automation

 

SIMOREG DC Master Base Drive Panel Operating Instructions

Page 163
Image 163
Siemens 6RA70 specifications Setting values for monitoring functions and limits, 10-42