Siemens 6RA70 specifications Configuration of serial interfaces on basic converter, 10-78

Models: 6RA70

1 232
Download 232 pages 59.99 Kb
Page 199
Image 199

PNU

Description

Value range

No. indices

See

 

 

[Unit]

Factory

Change

 

 

Steps

setting

(Access /

 

 

 

Type

Status)

10.40 Configuration of serial interfaces on basic converter

G-SST 1 (RS485 / RS232 on X300) (see also Section 8, Sheet G170 and Section 9 of Operating Instructions 6RX1700-0AD**)

 

 

 

0, 2, 8, 9

 

 

 

 

P780

Selection of protocol for G-SST1 basic converter interface

Ind: None

 

P052 = 3

*

0

Setting has no function

1

 

FS=2

 

P051 = 40

(G170)

 

 

Type: O2

 

Offline

2

USS protocol

 

 

 

 

 

 

 

 

 

 

8

for factory purposes

 

 

 

 

 

 

9

For internal factory test purposes

 

 

 

 

 

 

 

 

 

 

 

 

P781

Number of process data for G-SST1

0 to 16

 

Ind: None

 

P052 = 3

*

When P780 = 0 or 9 is selected: Parameter is irrelevant

1

 

FS=2

 

P051 = 40

(G170)

 

 

Type: O2

 

Offline

 

 

 

 

 

 

When USS protocol (P780=2) is selected: Number of PZD elements

 

 

 

 

 

 

0

No process data are expected or sent in the USS protocol

 

 

 

 

 

 

1...16 Number of process data words in USS protocol (same number

 

 

 

 

 

 

 

applies to transmission and receipt)

 

 

 

 

 

 

 

The received PZD elements (1 to max. 16) are available at

 

 

 

 

 

 

 

connectors (K2001 to K2016) and, in some cases, bit-serially at

 

 

 

 

 

 

 

binectors for "internal wiring" purposes.

 

 

 

 

 

 

 

The PZD elements to be transmitted (1 to max. 16) are selected

 

 

 

 

 

 

 

in parameters P784.01 to P784.16.

 

 

 

 

 

 

 

 

 

 

 

 

P782

Length of parameter jobs for G-SST1

0, 3, 4, 127

 

Ind: None

 

P052 = 3

*

 

 

1

 

FS=127

 

P051 = 40

(G170)

This parameter is effective only when P780=2 (USS protocol).

 

 

Type: O2

 

Offline

 

0

No PKW data are expected or sent in the USS protocol.

 

 

 

 

 

 

3, 4

3 or 4 PKW data words are expected in the USS protocol and 3

 

 

 

 

 

 

 

or 4 PKW data words are also sent (for transmission of

 

 

 

 

 

 

 

parameter values).

 

 

 

 

 

 

127

Number of PKWs is determined by the telegram length

 

 

 

 

 

 

 

 

 

 

 

 

P783

Baud rate for G-SST1

1 to 13

 

Ind: None

 

P052 = 3

*

1

300 baud

1

 

FS=6

 

P051 = 40

(G170)

 

 

Type: O2

 

Offline

2

600 baud

 

 

 

 

 

 

 

 

 

 

3

1200 baud

 

 

 

 

 

 

4

2400 baud

 

 

 

 

 

 

5

4800 baud

 

 

 

 

 

 

6

9600 baud

 

 

 

 

 

 

7

19200 baud

 

 

 

 

 

 

8

38400 baud

 

 

 

 

 

 

9

56700 baud

 

 

 

 

 

 

11

93750 baud

 

 

 

 

 

 

13

187500 baud

 

 

 

 

 

 

 

 

 

 

 

 

P784

Source for transmit data for G-SST1

All connector

 

Ind: 16

 

P052 = 3

*

Selection of connectors to be transferred as transmit data to the USS

numbers

 

FS=

 

P051 = 40

(G170)

1

 

i001: 32

 

Offline

master via USS interface 1.

 

 

 

 

 

i002: 167

 

 

 

i001:

Selection for word 1

 

 

i003: 0

 

 

 

 

 

i004: 33

 

 

 

i002:

Selection for word 2

 

 

 

 

 

 

 

i005-i016: 0

 

 

 

...

 

 

 

 

 

 

Selection for word 16

 

 

Type: L2

 

 

 

i016:

 

 

 

 

 

 

Applicable settings:

 

 

 

 

 

 

0 = connector K0000

 

 

 

 

 

 

1 = connector K0001

 

 

 

 

 

 

etc.

 

 

 

 

 

 

 

 

 

 

 

 

 

P785

Options for G-SST1

0 to 1

 

Ind: 2

 

P052 = 3

 

i001:

0 = Bus terminator OFF

1

 

FS=0

 

P051 = 40

 

 

 

Type: O2

 

Offline

(G170)

 

1 = Bus terminator ON

 

 

 

 

 

 

 

 

 

 

i002:

0 = Bit 10 of the 1st receive word does not function as "Control

 

 

 

 

 

 

 

by PLC".

 

 

 

 

 

 

 

1 = Bit 10 of the 1st receive word does function as "Control by

 

 

 

 

 

 

 

PLC“, i.e. when bit 10 = 0, all other bits of the 1st receive word,

 

 

 

 

 

 

 

as well as receive words 2 to 16, are not written to connectors

 

 

 

 

 

 

 

K2001 to K2016, or to binectors B2100 to B2915. All these

 

 

 

 

 

 

 

connectors and binectors retain their old values.

 

 

 

 

 

 

 

 

 

 

 

 

10-78

 

 

 

SIEMENS Energy & Automation

 

 

SIMOREG DC Master Base Drive Panel Operating Instructions

Page 199
Image 199
Siemens 6RA70 specifications Configuration of serial interfaces on basic converter, 10-78