PNU

Description

Value range [Unit] Steps

No. indices Factory setting Type

See Change (Access / Status)

r069

Serial number of SIMOREG DC Master converter

(G101)

i001:

1st and 2nd places of serial number

i002:

3rd and 4th places of serial number

 

 

i003:

5th and 6th places of serial number

 

i004:

7th and 8th places of serial number

 

i005:

9th and 10th places of serial number

 

i006:

11th and 12th places of serial number

 

i007:

13th and 14th places of serial number

 

i008 to i015:

0

 

i016:

Checksum for serial number

 

The serial number ASCII code is displayed in this parameter. The number is

 

output in plaintext on the OP1S panel.

 

 

r070

MLFB (order number) of SIMOREG DC Master converter

(G101)

The corresponding MLFB is displayed in encoded form in this parameter.

The MLFB is displayed in plaintext on the OP1S panel.

 

 

 

r071

Converter rated supply voltage (armature)

(G101)

Converter rated supply voltage (armature) as specified on rating plate

 

 

 

r072

Converter rated DC current (armature)

(G101)

i001:

Converter rated DC current (armature) as specified on rating

 

plate (output DC current at power terminals 1C1 and 1D1)

 

 

 

i002:

Actual converter rated DC current (armature) according to

 

 

setting in parameter P076.001 or P067

 

 

r073

Converter rated DC current (field)

(G101)

i001:

Converter rated DC current (field) as specified on rating plate

 

(output DC current at power terminals 3C and 3D)

 

 

 

i002:

Actual converter rated DC current (field) as set in parameter

 

 

P076.002

r074

Converter rated supply voltage (field)

(G101)

Converter rated supply voltage (field) as specified on rating plate

 

 

 

P075

Control word for power section

*Selection of operating characteristics of thermal monitor (I2t monitoring) of

(G101)

power section (see also Section 9.16 ”Dynamic overload capability of power

section”).

(G161)

The ”Dynamic overload capability of the power module“ allows the

 

 

SIMOREG DC Master to operate for short periods on armature currents that

 

are higher than the converter rated DC current specified on the rating plate

 

(=r072.001).

 

The permissible overload period is determined solely by the power module

 

and the preceding operating history.

 

The "thermal power module monitoring" function does not monitor operation

 

in compliance with the load class criteria set in parameter P067. If permitted

 

by the power module, the unit can operate for overload periods in excess of

 

those defined by the load class.

0Dynamic overload capability is not permitted

The armature current is limited to P077 * r072.001.

1Dynamic overload capability is permitted, alarm A039

The armature current is limited to P077 * 1.8 * r072.001 as long as the calculated thyristor temperature does not exceed the permitted value.

If the temperature exceeds the permitted value, the SIMOREG DC Master protects itself by reducing the current limit to P077 * r072.001. Alarm A039 is output at the same time.

The armature current setpoint limit is not increased to P077 * 1.8 * r072.001 (alarm A039 also disappears) until the calculated thyristor temperature has dropped below the limit value again and the armature current setpoint is lower than the converter rated DC current (r072.001).

2Dynamic overload capability is permitted, fault F039

The armature current is limited to P077 * 1.8 * r072.001 as long as the calculated thyristor temperature does not exceed the permitted value.

Fault message F039 is output if the permissible temperature limit is exceeded.

0 to 120

1

10 to 830 [V]

1V

0.0to 6553.5

[A]

0.1A

0.00to 100.00

[A]

0.01A

10 to 460 [V]

1V

0 to 2

1

Ind: 16

P052 = 3

Type: L2

 

Ind: None

P052

= 3

Type: O2

 

 

 

 

 

Ind: None

P052

= 3

Type: O2

 

 

 

 

 

Ind: 2

P052

= 3

Type: O2

 

 

 

 

 

Ind: 2

P052

= 3

Type: O2

 

 

 

 

 

Ind: None

P052

= 3

Type: O2

 

 

 

 

 

Ind: None

P052

= 3

FS=1

P051

= 40

Type: O2

off-line

SIEMENS Energy & Automation

10-15

SIMOREG DC Master Base Drive Panel Operating Instructions

 