P076

 

Reduction of converter rated DC current

see column on left

Ind: 2

P052 = 3

*

 

i001:

Reduction of converter rated DC current (armature)

 

 

FS=100.0

P051 = 40

 

 

 

 

 

Type: O2

Offline

 

(G101)

 

i002:

Reduction of converter rated DC current (field)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For the purpose of achieving a close match between the converter and

 

 

 

 

 

 

 

motor, the converter rated DC current is reduced to the value entered here.

 

 

 

 

 

 

 

The current value of the device rated DC is indicated in parameter r072.002.

 

 

 

 

 

 

 

The following values can be set:

 

 

 

 

 

 

10.0%, 20.0%, 33.3%, 40.0%, 50.0%, 60.0%, 66.6% 70.0%, 80.0%, 90.0%

 

 

 

 

 

 

 

and 100.0%

 

 

 

 

 

 

 

Note:

 

 

 

 

 

 

 

 

If a load class is selected in parameter P067 which causes a reduction in

 

 

 

 

 

 

 

the converter rated DC current, then the lower of the two parameter setting

 

 

 

 

 

 

 

values is effective.

 

 

 

 

 

 

 

 

 

 

 

 

 

P077

 

Total thermal reduction factor

 

0.50 to 1.00

Ind: None

P052 = 3

 

 

 

The factor set in this parameter effects a reduction in the armature current

0.01

FS=1.00

P051 = 40

 

(G101)

 

 

 

Type: O2

Offline

 

 

limit (as defined by the setting in P075).

 

 

 

(G161)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The converter must be derated in the following instances:

 

 

 

 

 

 

 

– Operation at high ambient temperatures:

 

 

 

 

 

 

 

If the ambient temperature is higher than 45°C (on naturally air-cooled

 

 

 

 

 

 

 

converters) or 35°C (on converters with forced air-cooling), the possible

 

 

 

 

 

 

 

load capability of the converter decreases as a consequence of the

 

 

 

 

 

 

 

maximum permissible thyristor junction temperature by percentage

 

 

 

 

 

 

 

reduction "a" as specified in the table in Section 3.4, resulting in a

 

 

 

 

 

 

 

temperature reduction factor of

 

 

 

 

 

 

 

ktemp = k1

 

 

 

 

 

 

 

– Installation altitudes of over 1000m above sea level:

 

 

 

 

 

 

 

In this case, the lower air density and thus less effective cooling reduce

 

 

 

 

 

 

 

the possible load capability of the converter to the percentage load "b1"

 

 

 

 

 

 

 

specified in the table in Section 3.4, resulting in an installation altitude

 

 

 

 

 

 

 

reduction factor of

 

 

 

 

 

 

 

kaltitude = k2

 

 

 

 

 

 

 

P077 must be set as follows: P077 = ktemp * kaltitude

 

 

 

 

 

 

 

Note:

 

 

 

 

 

 

 

 

A general reduction in the converter rated DC current (through appropriate

 

 

 

 

 

 

 

setting of parameter P076.001) can be included in this calculation.

 

 

 

 

 

 

 

 

 

 

 

 

 

P078

 

Reduction of converter rated supply voltage

 

i001: 10 to r071

Ind: 2

P052 = 3

 

 

 

i001:

Rated input voltage converter armature

 

i002: 10 to r074

FS=

P051 = 40

 

(G101)

 

 

[V]

i001: r071

Offline

 

 

i002: Rated input voltage converter field

 

 

 

 

 

1V

i002: 400V

 

 

 

 

The rated voltage value of the power system actually used to supply the

 

 

except when

 

 

 

 

 

 

r071 = 460V

 

 

 

 

power section must be set in this parameter.

 

 

 

 

 

 

 

 

then 460V

 

 

 

 

This setting acts as the reference for the undervoltage, overvoltage and

 

 

 

 

 

 

 

 

Type: O2

 

 

 

 

phase failure monitoring functions (see also P351, P352 and P353) as well

 

 

 

 

 

 

as for connectors K0285 to K0289, K0291, K0292, K0301 K0302, K0303

 

 

 

 

 

 

 

and K0305

 

 

 

 

 

 

 

NOTE

 

 

 

 

 

 

 

If a SIMOREG converter is operated at a rated input voltage that is

 

 

 

 

 

 

lower than its rated supply voltage, then the rated DC voltage specified

 

 

 

 

 

 

in the technical data (Section 3.4) cannot be reached !

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P079

Short pulses / long pulses, armature gating unit

0 to 1

Ind: None

P052 = 3

*

0

Short pulses (0.89 ms=approx. 16 degrees at 50 Hz) are output

1

FS=0

P051 = 40

 

 

Type: O2

Offline

(G163)

 

 

on the armature gating unit.

 

 

 

 

 

 

 

1

Long pulses (pulse duration up to approx. 0.1 ms before next

 

 

 

 

 

 

pulse) are output on the armature gating unit (e.g. required in

 

 

 

 

 

 

cases where field is supplied via armature terminals).

 

 

 

10-16

SIEMENS Energy & Automation

 

SIMOREG DC Master Base Drive Panel Operating Instructions

Page 137
Image 137
Siemens 6RA70 10-16, P077 Total thermal reduction factor, Temp = k1, P078 Reduction of converter rated supply voltage