6RA70 DC MASTER

 

 

 

 

 

 

 

 

 

 

 

SIMPLIFIED BLOCK DIAGRAM

 

 

 

 

 

 

 

 

 

 

(ALL AVAILABLE FUNCTIONS ARE NOT SHOWN ON SIMPLIFIED BLOCK DIAGRAM)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<1>

 

 

 

 

 

 

 

 

 

ACTUAL EMF

 

 

 

 

 

ACTUAL FIELD

 

 

 

 

 

 

 

 

 

 

iax R a

 

 

 

CURRENT

 

 

 

 

 

 

 

 

 

r037

 

r038

 

 

 

 

 

 

 

 

 

EMF

 

 

 

 

r035

FIELD

 

 

 

 

 

ACTUAL VALUE

 

 

 

 

 

 

 

 

ACTUAL VALUE

 

 

 

 

 

P616 (286)

 

EMF

 

 

 

ARMATURE TERMINAL

 

P612 (266)

 

INTERNAL

 

 

 

K

K286

 

 

 

 

 

K

K266

FIELD ACTUAL

 

 

 

 

 

 

 

VOLTAGE

 

 

 

 

 

 

 

 

 

 

 

 

K265

 

 

 

CURRENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K285

 

EMF

 

dia x La

 

 

 

P120.F - P139.F

FLUX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[ 3.3 ]

K0287

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K290

[ 3.6 ]

 

 

 

 

 

 

 

dt

 

 

 

 

 

 

 

 

 

EMF CONTROLLER

 

 

 

 

 

FIELD CURRENT CONTROLLER

FIELD

 

 

DROOP

FIELD

 

 

 

 

 

 

 

 

 

 

LINE VOLTAGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P277.F (0)

WEAKENING

RATED MOTOR

 

<1>

 

 

 

 

 

 

EMF

 

K P

TN

ACTIVE

 

FIELD CURRENT

 

FIELD

KP

TN

 

ADVANCE

 

SETPOINT

 

P275.F (.6)

P276.F (.2)

P081 (0)

 

 

P102.F (0 A)

 

CURRENT

P255.F (5)

P256.F (.2)

 

LIMIT

 

 

 

 

 

 

 

 

SETPOINT

 

 

 

 

P250.F (00 )

 

r039

 

 

 

100%

 

 

 

FIELD

 

 

 

 

 

 

 

 

 

 

 

r036

 

 

 

 

r034

 

P100.F X P110.F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ECONOMY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

K277

K276

 

 

 

 

 

 

 

 

-

K288

K283

K280

K0275

0

K268

K263

 

K260

K251

K250

 

K278

 

 

 

 

 

 

 

 

 

 

 

P101.F

 

EMF

 

1

 

 

 

 

 

 

CURRENT

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

CONTROLLER

 

 

 

 

 

 

CONTROLLER

 

 

 

Sheet 5 EMF and Field Current Control

SIMOREG DC

ADDITIONAL EMF

 

 

P103.F (0 A )

P257.F (0 %)

 

ADDITIONAL

MINIMUM FIELD

STANDSTILL

SETPOINT

 

 

FIELD CURRENT

CURRENT

FIELD

P615 (0)

 

SETPOINTS

 

 

K

ENABLE

P611 (0)

 

1

K

 

Index .02 - .04

 

 

P273 (1)

 

 

 

Index .02 - .04

 

 

 

 

 

 

CURRENT SETPOINT IS SET TO ZERO WHEN FIELD GATE PULSES ARE DISABLED

FIELD

RESISTANCE

P112.F (0)

P251.F (1800 )

RETARD

LIMIT

Master Base Drive Panel Operating

Siemens Energy &

Instructions

Automation

 

 

 

 

 

 

 

 

 

 

 

P692.B (0)

 

 

 

 

FIELD

 

 

 

 

B

 

 

 

 

 

SETPOINT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K293

LINE CONTACTOR

 

 

 

 

 

 

 

 

 

 

 

SPEED

K166

 

 

 

 

CLOSED

 

 

 

 

 

 

 

 

 

 

ABSOLUTE

 

 

 

 

 

n

 

B0124

 

 

VALUE

n

 

 

 

 

 

 

 

 

 

&

 

 

 

 

P118.F (340)

P119.F (100)

P120.F

P082=2

t

 

 

 

 

 

 

 

 

 

 

 

 

 

RATED

BASE

to

 

 

 

 

 

 

 

EMF

SPEED

P139.F

 

 

P258.F (10s)

 

 

 

 

 

 

 

 

 

 

 

 

FIELD

Delay time

CHARACTERISTICS

 

<1> 100% CORRESPONDS TO THE RATED MOTOR FIELDCURRENT (P102)

 

K304

FIELD

LINE VOLTAGE

FEED FORWARD

K271

P253.F (1)

ENABLE

MOTOR FIELD

5

Page 221
Image 221
Siemens 6RA70 specifications 11-6, Sheet 5 EMF and Field Current Control